LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal Legend

Function/Description

AC/AC

Low voltage AC input (24VAC or 28VAC / 175VA).

– DC +

12VDC / 24VDC @ 6A continuous output.

AC FAIL 

NC, C, NO

Used to notify loss of AC power, (e.g. connect to audible device or alarm panel).

Relay normally energized when AC power is present. Contact rating 1A @ 28VDC.

Low Battery 

NC, C, NO

Used to indicate low battery condition, (e.g. connect to alarm panel). 

Relay normally energized when DC power is present. Contact rating 1A @ 28VDC

– BAT +

Stand-by battery connections. Maximum charge rate 0.7A.

Fig. 1

Fig. 1a

---  DC + 

---  BAT + 

 

AC

AC

15

AC  DC

OFF  24VDC

ON  12VDC

ON

NC    C    NO NC    C    NO

BAT FAIL

AC FAIL

---  DC + 

---  BAT + 

 

AC

AC

15

AC  DC

OFF  24VDC

ON  12VDC

ON

NC    C    NO NC    C    NO

BAT FAIL

AC FAIL

Altronix is not responsible for any typographical errors.

––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056

website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty 

IISMP7PM Rev. 061603 