background image

Voltage Output/Transformer Selection Table:

Output VDC

Switch Position

Max. Load DC

Transformer Requirements

(Recommended Altronix Part #’s)

12VDC

SW1 ON

6A

24VAC or 28VAC / 175VA (T2428175)

24VDC

SW1 OFF

6A

24VAC or 28VAC / 175VA (T2428175)

Installation Instructions:

SMP7PM should be installed in accordance with The National Electrical Code and all applicable Local 

Regulations.

1. Mount SMP7PM in the desired location/enclosure (mounting hardware included).

2. Set SMP7PM to the desired DC output voltage by setting the SW1 switch 

(Fig. 1a, pg. 2) 

to the 

  appropriate position 

(Voltage Output/Transformer Selection Table). 

Adjust output voltage by using the trimpot 

  on the power supply board 

(Fig. 1a, pg. 2) 

prior to connecting devices.

3. Connect proper transformer to the terminals marked [AC] 

(Voltage Output/Transformer Selection Table).

  Use 18 AWG or larger for all power connections (Battery, DC output).

 

Keep power-limited wiring separate from non power-limited wiring 

  (115VAC/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.

  CAUTION: Do not touch exposed metal parts. 

  Shut branch circuit power before installing or servicing equipment.

  There are no user serviceable parts on the board. 

  Refer installation and servicing to qualified service personnel.

4. Measure output voltage before connecting devices. This helps avoiding potential damage.

5. Connect devices to be powered to the terminals marked [– DC +]. 

6. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to the 

  terminals marked [– BAT +] on the board (battery leads included). Use two (2) 12VDC batteries connected in 

  series for24VDC operation.

 

Note:

 When batteries are not used, a loss of AC will result in the loss of output voltage.

7. Connect appropriate trouble reporting devices to AC Fail & Low battery supervisory relay outputs marked

  [NC, C, NO]. Use 22 AWG to 18 AWG for AC Fail / Low Battery reporting.

  AC Failure will report in 5 minutes. For a 6 hour delay on reporting cut resistor J1.

SMP7PM

Supervised Power Supply/Charger

Installation Guide

Overview:

Altronix SMP7PM is a supervised power supply that converts a low voltage AC input into 12VDC or 24VDC output 

with 6A continuous supply current.

Specifications:

Input:

•  Input 28VAC

 

(Voltage Output/Transformer Selection Table)

.

Output:

•  12VDC or 24VDC selectable output. 

•  6A supply current. 

•  Output fuse is rated 15A/32V. 

•  Filtered and electronically regulated outputs.

•  Short circuit and thermal overload protection.

Supervision:

•  AC fail supervision (form “C” contacts). 

•  Battery presence and low battery supervision 

  (form “C” contacts).

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Maximum charge current 0.7A.

•  Zero voltage drop when switching over 

  to battery backup.

Indicators:

•  AC input and DC output LED indicators.

Board Dimensions 

(W x L x H approximate)

:

  7” x 4.25” x 1.25” (177.8mm x 108mm x 31.8mm).
* Specified at 25˚C ambient.

Отзывы: