LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal Legend

Function/Description

AC/AC

Low voltage AC input (24VAC or 28VAC / 175VA).

– DC +

12VDC / 24VDC @ 6A continuous output.

– BAT +

Stand-by battery connections. Maximum charge rate 0.7A.

---  DC + 

---  BAT + 

 

AC

AC

15

AC  DC

OFF  24VDC

ON  12VDC

ON

Fig. 1

Fig. 1a

---  DC + 

---  BAT + 

 

AC

AC

15

AC  DC

OFF  24VDC

ON  12VDC

ON

Altronix is not responsible for any typographical errors.

––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––