LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal Legend
Function/Description
AC/AC
Low voltage AC input (24VAC or 28VAC / 175VA).
– DC +
12VDC / 24VDC @ 6A continuous output.
– BAT +
Stand-by battery connections. Maximum charge rate 0.7A.
--- DC +
--- BAT +
AC
AC
15
AC DC
OFF 24VDC
ON 12VDC
ON
Fig. 1
Fig. 1a
--- DC +
--- BAT +
AC
AC
15
AC DC
OFF 24VDC
ON 12VDC
ON
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––