SMP5CTX220

Overview:

Altronix SMP5CTX220 and SMP5PMCTX220 power supply/chargers convert 115VAC or 230VAC (working 

range 198VAC - 256VAC), 50Hz/60Hz input into a regulated 12VDC or 24VDC output with 4A of continuous 

load current (see specifications).

Specifications:

Agency Listing:

•  CE European Conformity. 

Input:

•  115VAC, 50/60Hz, 0.95A or 230VAC (working 

  range 198VAC - 256VAC), 50/60Hz, 0.5A.

Output:

•  12VDC or 24VDC selectable output. 

•  4A supply current. 

•  Filtered and electronically regulated outputs.

•  Short circuit and thermal overload protection.

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Zero voltage drop when switching over to 

  battery backup.

Visual Indicators:

•  AC input and DC output LED indicators.

Supervision (SMP5PMCTX220 only):

•  AC fail supervision (form “C” contacts).

•  Low battery supervision (form “C” contacts).

Environmental:

•  Operating temperature: 0ºC to 49ºC (32ºF to 120ºF).

•  Storage temperature: -20ºC to 70ºC (-4ºF to 158ºF).

•  Relative humidity: 85% +/-5%.

Electrical:

•  System AC input VA requirement:

  -  115VAC: 109.25VA.

  -  230VAC: 115VA.

Mechanical:

•  Enclosure Dimensions (H x W x D approx.):

  13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)

  -  Accommodates up to two (2) 

  12VDC/7AH 

batteries.

Power Supply Voltage Output Specifications:*

Output VDC

Switch Position

Max. Load DC

12VDC

SW1 - ON (Fig. 1b, pg. 2)

4A

24VDC

SW1 - OFF (Fig. 1b, pg. 2)

4A

*Specified at 25˚ C ambient.

Installation Instructions:

Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and 
with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
 

in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

 

the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

 

two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s 

 

upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 4). Secure enclosure to earth ground. 

2.  Slide [Power ON/OFF] switch t o OFF position.
3.  Set SW1 on the power supply board to the desired DC output voltage (Fig. 1b, pg. 3)
 

(Power Supply Voltage Output Specification Chart).

4.  Connect AC circuit (115VAC or 230VAC, 50Hz/60Hz) as follows: Green branch wire connects to ground 
 

lug    . Line and Neutral to the connector on power supply board marked [L, N] respectively.

 

Use 18 AWG or larger for all power connections (Battery, DC output).

 

Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

5.  Slide [Power ON/OFF] switch to ON position.
6.  Measure output voltage before connecting devices. This helps avoiding potential damage.
 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 

 

equipment. There are no user serviceable parts inside. 

 

Refer installation and servicing to qualified service personnel.

7.  Slide [Power ON/OFF] switch t o OFF position.
8.  Connect devices to be powered to the terminals marked [– DC + ] carefully observing correct polarity.
 

Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board.

 

When servicing the unit, AC mains should be removed.

9.  When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked 
 

[– BAT +] (battery leads included). 

12VDC operation: Use one (1) 12VDC battery. 

 

24VDC operation: Use two (2) 12VDC batteries connected in series.

 

Note: When batteries are not used, a loss of AC will result in the loss of output voltage.

10. 

SMP5PMCTX220 Only: Connect appropriate signaling notification devices to AC Fail and Low Bat 

 

supervisory relay outputs marked [NC, C, NO] (Fig. 1a, pg. 2).

11.  Slide [Power ON/OFF] switch to ON position.

LG

N

OFF    ON

LOW BAT

NC    C   NO     NC   C     NO

AC FAIL

5A 250V

OFF - 24V

ON - 12V

ON

--- 

 BAT  

+-

-- 

 DC  

+

AC

DC

Power Supply

Board

115/230VAC 

power mains

Ground

Lug

Power

Distribution

Module(s)

Optional Rechargeable

Stand-by Battery

Optional Rechargeable

Stand-by Battery