LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating conditions
ON
OFF
Loss of AC. Stand-by battery supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal
Legend
Function/Description
AC/AC
Low voltage AC input (see voltage output/transformer selection table).
For 6VDC output use 16VAC or higher with 40VA power rating or higher.
For 12VDC output use 16VAC or higher with 85VA power rating or higher.
For 24VDC output use 28VAC with 175VA power rating or higher.
Caution: Do not apply voltage above 28VAC or 45VDC (maximum input rating).
+ DC --
6VDC, 12VDC or 24VDC @ 4A continuous supply current.
+ BAT --
Stand-by battery connections. Maximum charge rate 300mA.
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.
IISMP5 - Rev. 020912
H25Q
MEMBER
+ DC -- + BAT -- AC AC
AC
DC
MADE IN U.S.A.
SW1
6 V
12 V
24 V
SW1
ON
OFF
OFF
SW2
OFF
OFF
ON
S
W
2
1 2
O N