Overview:
These units convert a 115VAC or 230VAC, 50/60Hz input into a regulated 12VDC or 24VDC output up to 2.5 amp of
continuous load current (see specifications).
SMP3CTX Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory Power Distribution Module(s)
Number of Outputs
Fused Outputs
PTC Outputs
Individual Output Rating
Supervised
115VAC/ 230VAC Input Current
12VDC/ 24VDC Total Output Current
SMP3CTX
----
1
----
----
----
---- 0.65 amp / 0.35 amp
2.5 amp
SMP3PMCTX
x
0.65 amp / 0.35 amp
2.5 amp
SMP3PMCTXX
0.65 amp / 0.35 amp
2.5 amp
SMP3PMP4
PD4
4
x
----
3.5 amp
x 0.65 amp / 0.35 amp
2.5 amp
SMP3PMP4CB
PD4CB
----
x
2.5 amp
x 0.65 amp / 0.35 amp
2.5 amp
SMP3PMP8
PD8
8
x
----
3.5 amp
x 0.65 amp / 0.35 amp
2.5 amp
SMP3PMP8CB
PD8CB
----
x
2.5 amp
x 0.65 amp / 0.35 amp
2.5 amp
SMP3PMP16
PD16W
16
x
----
3.5 amp
x 0.65 amp / 0.35 amp
2.5 amp
SMP3PMP16CB PD16WCB
----
x
2.5 amp
x 0.65 amp / 0.35 amp
2.5 amp
Specifications:
Power Supply Voltage Output Specifications:*
Output VDC
Switch Position
Max. Load DC
12VDC
SW1 - Closed (Fig. 1b, pg. 3)
2.5 amp
24VDC
SW1 - Open (Fig. 1b, pg. 3)
2.5 amp
*Specified at 25˚ C ambient.
Installation Instructions:
Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 4).
Secure enclosure to earth ground.
2. Set SW1 on the power supply board to the desired DC output voltage (Fig. 1c, pg. 3) (Power Supply Voltage
Output Specification Chart).
3. Connect AC power to the terminals marked [L & N], connect ground to the green flying lead (Fig. 1, pg. 3).
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
• Universal 115VAC/230VAC input.
• Maximum charge current 0.5 amp.
• Filtered and electronically regulated outputs.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when
AC fails (zero voltage drop).
• AC input and DC output LED indicators.
• Short circuit and thermal overload protection.
• Complete with power supply, power distribution module
(when applicable), enclosure, cam lock & battery leads.
• Power on-off switch.
Supervised models only:
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
SMP3CTX Series - Installation Guide