- 4 - 

SMP3CTX Series Installation Guide

Terminal Identification:

Power Supply Board:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral.

–  DC +

12VDC / 24VDC @ 2.5A continuous output.

*AC FAIL 

NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. 

Relay normally energized when AC power is present. 

Contact rating 1A @ 120VAC / 28VDC.

*Low Battery 

NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally

energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC.

Low battery threshold:

12VDC output threshold set @ approximately 10.5VDC, 

24VDC output threshold set @ approximately 21VDC.

– BAT +

Stand-by battery connections. Maximum charge rate 0.5A.

*Note:

 Supervised models only

PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:

Terminal Legend

Function/Description

PD4/PD4CB

PD8/PD8CB

PD16W/PD16WCB

1P to 4P

1P to 8P

1P to16P

Positive DC power outputs.

1N to 4N

1N to 8N

1N to 16N

Negative DC power outputs.

Caution: Equipment to be installed / serviced by authorized / trained personnel only. 

Shut branch circuit power before installing / servicing equipment.

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. 

This installation should be made by qualified service personnel and should conform to the National 

Electrical Code and all local codes.

The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user 

to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of 

sufficient magnitude to constitute an electric shock.

The exclamation point within an equilateral triangle is intended to alert the user to the presence of impor-

tant operating and maintenance (servicing) instructions in the literature accompanying the appliance.

CAUTION:

 To reduce the risk of electric shock do not open enclosure. 

There are no user serviceable parts inside. 

Refer servicing to qualified service personnel.

Содержание SMP3CTX Series

Страница 1: ...e ___________________ SMP3CTX Series Power Supply Chargers Models Include SMP3CTX SMP3PMCTX SMP3PMCTXX Single Output SMP3PMP4 Four 4 Fuse Protected Outputs SMP3PMP8 Eight 8 Fuse Protected Outputs SMP3PMP16 Sixteen 16 Fuse Protected Outputs SMP3PMP4CB Four 4 PTC Protected Outputs SMP3PMP8CB Eight 8 PTC Protected Outputs SMP3PMP16CB Sixteen 16 PTC Protected Outputs Installation Guide ...

Страница 2: ...4VDC SW1 OFF Fig 1c pg 5 2 5A Specified at 25 C ambient Agency Listings CE European Conformity Input Input 115VAC 50 60Hz 0 65A or 230VAC 50 60Hz 0 35A Output 12VDC or 24VDC selectable output 2 5A supply current Filtered and electronically regulated outputs Short circuit and thermal overload protection Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge curren...

Страница 3: ...osed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified service personnel 7 Slide Power ON OFF switch t o OFF position 8 Connect devices to be powered a For Power Supply Board connect to the terminals marked DC b For Power Distribution Module s connect devices to be powered to the t...

Страница 4: ...B 1P to 4P 1P to 8P 1P to16P Positive DC power outputs 1N to 4N 1N to 8N 1N to 16N Negative DC power outputs Caution Equipment to be installed serviced by authorized trained personnel only Shut branch circuit power before installing servicing equipment WARNING To reduce the risk of fire or electric shock do not expose the unit to rain or moisture This installation should be made by qualified servi...

Страница 5: ...ttery OFF ON L 5A 250V Green OFF 24V ON 12V ON LOW BAT NC C NO NC C NO AC FAIL BAT DC AC DC Board 115VAC 230VAC power mains P Dist Mo Optional Rechargeable Stand by Battery Option Sta OFF 24V ON 12V ON BAT DC Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery Fig 1 Fig 1a Switch disables power mains line voltage input If stand by battery batteries are connected the DC ou...

Страница 6: ...R OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED ON OFF SW1 Used on PTC Models DC Output to devices From Power Supply Board Factory Installed Power Distribution Module s common outputs protected outputs P N N P S XFM R I n pu t 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 P N 3 5A 250V For continuous protection against risk of fire replace fuses with same type and rating Used on PTC Model...

Страница 7: ...re accommodates up to two 2 12VDC 7AH batteries 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm 1 20 30 5mm ...

Страница 8: ...mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 905...

Отзывы: