SMP1024Xseries 

- 3 - 

4.  Connect devices to be powered:
  a. For Power Supply Board connect to the terminals marked [---  DC +]. 
  b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked  
    [1P & 1N] through [4P & 4N] (Fig. 2, pg. 4), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 4),  
    or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 5, pg. 5) carefully observing correct polarity.
5.  When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [---  BAT +] 
  (battery leads included), (Fig. 1, pg. 4 or Fig. 4, pg. 5)
  Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
6.  For Supervised Models Only: 
  Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs marked 
  [N.O., C, N.C.] (Fig. 1a, pg. 4, Fig. 4a, pg. 5).

LED Diagnostics:

OLS250/OLS257 - Power Supply Board

Red (DC)

Green (AC) Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

Terminal Identification:

OLS250/OLS257 - Power Supply Board

Terminal Legend Function/Description
L, G, N

Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground (if used).

---  DC +

24VDC @ 10 amp total supply current.

*AC FAIL

N.C., C, N.O.

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally

energized when AC power is present. Contact rating 1 amp @ 120VAC / 28VDC.

*Low Battery

N.C., C, N.O.

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized

when DC power is present.

Contact rating 1 amp @ 120VAC / 28VDC. Low battery threshold: 

24VDC output threshold set @ approximately 21VDC.

---  BAT +

Stand-by battery connections. Maximum charge rate 0.7 amp.

*Note: Supervised Models  Only.

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Terminal Legend

Function/Description

PD4/PD4CB

PD8/PD8CB

PD16W/PD16WCB

1P to 4P

1P to 8P

1P to 16P

Positive DC power outputs.

1N to 4N

1N to 8N

1N to 16N

Negative DC power outputs.

Содержание SMP10PM24X Series

Страница 1: ...ent with supervision with supervision Four 4 fuse protected outputs Four 4 PTC protected outputs SMP10PM24P8 SMP10PM24P8CB 24VDC 10 amp total supply current 24VDC 10 amp total supply current with supe...

Страница 2: ...three fasteners Place the enclosure s upper keyholes over the two upper screws Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pgs 6 Secure enclosure to earth gro...

Страница 3: ...wer OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output PD4 PD4CB PD8 PD8CB Power Distribution Module Green Power Distribution Module Status ON Normal operating condi...

Страница 4: ...tional rechargeable stand by batteries must match the power supply output voltage setting INPUT LED 1P 2P 3P 4P FUSED OUTPUTS 1N 2N 3N 4N COMMON OUTPUTS F1 F1 F2 F3 F4 COMMON POWER OUTPUTS 1P 1N 2P 2N...

Страница 5: ...ply output voltage setting Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery Fig 4 Fig 4a LOW BAT NC C NO NC C NO OFF ON 5A 250V AC FAIL BAT DC 15 AC DC Power Distribution...

Страница 6: ...two 2 12VDC 7AH batteries 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25...

Страница 7: ...SMP1024Xseries 7 Notes...

Страница 8: ...ographical errors Product specifications are subject to change without notice 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix c...