Terminal Identification:

Terminal Legend Function/Description

AC/AC

Low voltage AC input (Voltage Output/Transformer Selection Table).
For 12VDC output use 28VAC or higher with 175VA power rating or higher.
For 24VDC output use 28VAC with 175VA power rating or higher.
Caution: Do not apply voltages above 28VAC (28VAC is maximum input rating).

– DC +

12VDC / 24VDC @ 10A continuous output.

AC FAIL 

NC, C, NO

Indicate loss of AC power, (e.g. connect to audible device or alarm panel). AC report delay is 

approx. 1 min. Relay normally energized when AC power is present. 

Contact rating 1A @ 120VAC / 28VDC.

Low Battery 

NC, C, NO

Indicate low battery or battery presence condition, (e.g. connect to audible device or alarm panel). 

Battery presence delay is approx. 3 mins. Circuit will restore 5 secs. after battery is detected. Relay 

normally energized during proper battery operation. Contact rating 1A @ 120VAC / 28VDC.

Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC, 24VDC output 

threshold set @ approximately 21VDC. Battery Presence: 12 or 24VDC battery presence threshold 

is approximately 4VDC. Battery presence is automatically tested about every 5 mins. If battery is 

determined absent, the unit will automatically test for presence about every 5 secs.

– BAT +

Stand-by battery connections. Maximum charge rate 0.7A.

---  DC + 

---  BAT + 

 

AC

AC

15

AC  DC

OFF  24VDC

ON  12VDC

ON

NC    C    NO NC    C    NO

BAT FAIL

AC FAIL

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.
IISMP10PM B27S

MEMBER

---  DC + 

---  BAT + 

 

AC

AC

15

AC  DC

OFF  24VDC

ON  12VDC

ON

NC    C    NO NC    C    NO

BAT FAIL

AC FAIL