ReServWP

LED Diagnostics:

Power Supply Board

Red (DC)

Green (AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

ReServ Board

LED

LED State

Unit Status

Output LEDs

ON

Normal operating condition.

OFF

Loss of 24VAC and/or 12VDC output power.

Low Battery

ON

Stand-by batteries are low.

OFF

Normal operating condition.

Shutdown

ON

Loss of 24VAC and/or 12VDC output power. Discharged stand-by battery.

OFF

Normal operating condition.

Audio Signal Diagnostics:

ReServ Unit

Audio Signal

Unit Status

Single Periodic Beep

AC Fail.

Double Periodic Beep

Low Battery or No Battery.

Terminal Identification:

Power Supply Board

Terminal
Legend

Function/Description

L, G, N

Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.

– DC +

24VDC non power-limited output. 

AC FAIL 
NO, C, NC

Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices. 
With AC present, terminals marked NO and C are open, NC and C are closed. 
When loss of AC occurs, terminals marked NO and C are closed, NC and C are open.

BAT FAIL 
NO, C, NC

Form “C” dry contacts used to signal low battery voltage or loss of battery voltage. 
Under normal conditions terminals marked NO and C are open, NC and C are closed. 
During a trouble condition terminals marked NO and C are closed, and NC and C are open.

+ BAT – 

Stand-by battery connections. Maximum charge current 0.7A.

ReServ Board

Terminal Legend

Function/Description

Input – 24VDC +

24VDC input from power supply board.

N, P 1-16

24VAC and/or 12VDC outputs. 

Содержание ReServ1WP

Страница 1: ... and Four 4 regulated 12VDC outputs 4A total supply current 24VAC and 2A total supply current 12VDC PTC protected power limited outputs ReServ2WP Sixteen 16 true sine wave regulated 24VAC outputs 4A total supply current PTC protected power limited outputs ReServ3WP Sixteen 16 regulated 12VDC outputs 8A total supply current PTC protected power limited outputs ...

Страница 2: ...pecifications Output PTC protected power limited outputs are rated 1A Battery Backup Built in charger for sealed lead acid or gel type batteries Automatic switchover to stand by battery when AC fails Supervision AC fail supervision form C contacts Low battery supervision form C contacts Visual and Audio Indicators AC DC power LED indicators Individual power output LED indicators Low voltage input ...

Страница 3: ...minals marked P 1 4 N 1 4 Fig 1 pg 5 Connect 24VAC cameras devices to the terminals marked 5 16 Fig 1 pg 5 ReServ2WP Connect 24VAC cameras devices to the terminals marked 1 16 Fig 1 pg 5 ReServ3WP Connect 12VDC cameras devices to the terminals marked P 1 16 N 1 16 Fig 2 pg 6 10 Connect batteries to the terminals marked BAT Figs 1 2 pg 5 6 Use two 2 12VDC batteries connected in series for 24VDC ope...

Страница 4: ...ery Terminal Identification Power Supply Board Terminal Legend Function Description L G N Connect 115VAC 60Hz to these terminals L to hot N to neutral DC 24VDC non power limited output AC FAIL NO C NC Form C dry contacts used to instantaneously signal the loss AC to local annunciation devices With AC present terminals marked NO and C are open NC and C are closed When loss of AC occurs terminals ma...

Страница 5: ...of used batteires according to the instructions 12VDC Rechargeable Battery order separately Note Two 2 12VDC rechargeable batteries connected in series required Supervised Non power limited Unswitched 115VAC 60Hz 3 5A power mains non power limited Green Lead L G N BAT DC NC C NO NC C NO Input 24VDC power limited Non power limited ...

Страница 6: ...rechargeable batteries connected in series required Supervised Non power limited Unswitched 115VAC 60Hz 3 5A power mains non power limited L G N BAT DC NC C NO NC C NO power limited Non power limited 12VDC Power Limited Outputs 24VDC P N 1 OUT 2 1 2V adjust P N 3 OUT 4 3 4V adjust P N 5 OUT 6 5 6V adjust P N 7 OUT 8 7 8V adjust P N 9 OUT 10 9 10V adjust P N 11 OUT 12 11 12V adjust P N 13 OUT 14 13...

Страница 7: ...op Pole Mount bracket is achieved tighten the straps down by sliding open end of the strap through the locking mechanism on the strap then tighten the screw with flat head screwdriver or 5 16 hex socket driver Fig 5 pg 7 and Fig 7 pg 7 3 Attach the bottom bracket to the enclosure by inserting bolts through the flange of the enclosure and into the bracket tightening bolts with a 7 16 hex socket Fig...

Страница 8: ...17 53 x 15 3 x 6 67 445 3mm x 388 6mm x 169 4mm FRONT VIEW COVER REMOVED RIGHT SIDE VIEW FRONT VIEW END VIEW SECTION A A A A 316 STAINLESS STEEL PADLOCK LATCH ATTACHED WITH RIVETS Ø 375 PADLOCK EYE 17 36 441 mm 12 00 304 8mm 6 41 162 8mm 10 32 X 250 BRASS INSERT 4 PLCS 14 54 369 3mm 16 74 425 2mm 0 125 3 2mm 14 25 362mm 14 00 355 6mm 12 23 310 6mm 17 53 445 3mm 16 00 406 4mm 1 67 42 4mm 5 00 127mm...

Отзывы: