Overview:

These Altronix Rack Mount CCTV Power Supplies provide 6-15VDC distributed via sixteen (16) fuse or PTC protected
outputs for powering CCTV Cameras, heaters and other video accessories.

Sixteen (16) Output Rack Mount Configuration Reference Chart:

R615DC416

4 amp

6-15VDC

16

-

x

3.5 amp

.9 amp

R615DC416CB

4 amp

6-15VDC

16

x

-

2.5 amp

.9 amp

R615DC616

6 amp

6-15VDC

16

-

x

3.5 amp

1.5 amp

R615DC616CB

6 amp

6-15VDC

16

x

-

2.5 amp

1.5 amp

R615DC1016

10 amp

6-15VDC

16

-

x

3.5 amp

1.9 amp

R615DC1016CB

10 amp

6-15VDC

16

x

-

2.5 amp

1.9 amp

Specifications:

• 2U rack mount chassis for use in standard EIA 19” rack.

• Filtered and electronically regulated outputs.

• Removable terminal blocks with locking screw flange.

• Short circuit and thermal overload protection.

• Power switch with built-in circuit breaker.

• Unit maintains camera synchronization.

• Sixteen (16) individual power LED indicators.

• Ease of installation saves time and eliminates costly labor.

Rack Dimensions:

3.25”H x 19.125”W x 8.5”D

Installation Instructions:

1. Unit is factory set at 12VDC. To adjust the output voltage remove the bottom cover to access trimpot on the 

power supply board 

(Fig. 1B, pg. 3)

.

2. Mount unit in desired rack location (Space unit at least 3” from any video monitors).
3. Set power switch on back of unit to the OFF position 

(Fig. 1E, pg. 3).

4. Plug power cord into grounded 115VAC 50/60 Hz receptacle (

Fig. 1D, pg. 3)

.

5. Set power switch to the ON (RESET) position and measure output voltage before connecting devices 

(

Fig. 1E, pg. 3)

. This helps avoid potential damage.

6. Set power switch on back of unit to the OFF position 

(Fig. 1E, pg. 3).

7. Connect devices to removable terminal blocks marked [1P & 1N through 16P & 16N]

(Fig. 1C, pg. 3)

.

When wiring is completed on terminal blocks they can be locked down by tightening screw flanges.
All terminals with common suffix (P) “1P, 2P...” are the same polarity (positive).
All terminals with common suffix (N) “1N, 2N...” are the same polarity (negative).

8. Upon completion of wiring, set power switch on back of unit to the ON (RESET) position 

(Fig. 1E, pg. 3)

.

9. Green power LEDs on faceplate will illuminate when AC power is present. When an output is in a trouble condition 

(blown fuse or tripped PTC) the corresponding LED will not be illuminated 

(Fig. 1, pg. 3)

.

a. Blown fuse (R615DC416) - Set power switch on back of unit to the OFF position (

Fig. 1E, pg. 3).

Remove front faceplate to access fuses. Replace with fuses rated @ 3.5A/250VA (Altronix model # Fuse1).

b. Tripped PTC (R615DC416CB) - To reset PTC, set power switch on back of unit to the OFF position. 

After approximately 30 secs. set power switch to the ON (RESET) position (

Fig. 1E, pg. 3)

.

10. Power switch with built-in circuit breaker:

OFF position - Switch not Illuminated. Outputs not powered.
RESET (ON) position - Switch illuminated. Outputs powered.
Circuit breaker tripped - Switch not Illuminated. Power LEDs on faceplate are not illuminated. Outputs not powered.
To reset circuit breaker set power switch to the ON (RESET) position (

Fig. 1E, pg. 3)

.

- 2 -

Altronix 
Model Number

Output Cur

rent

(max per output)

Total Output Cur

rent

(P

ow

er)

Output 

V

oltage

115V

A

C

50/60Hz Input

Cur

rent

PTC Protected

Outputs Fuse Protected

Outputs

Number of 

Ouputs