Overview:

Altronix R1224DC68220 Series Rack Mount Power Supplies provides 12VDC or 24VDC @ 6A via eight (8) 
fuse or PTC protected outputs for powering CCTV cameras, heaters, and other video accessories.

Eight (8) Output Rack Mount Configuration Reference Chart:

Altronix 
Model Number

Total Output 

Current (Power)

Output Voltage 

(VDC)

Number of 

Outputs

PTC 

Protected 

Outputs

(auto-

resettable)

Fuse 

Protected

Outputs

Individual 

Output 

Current (max 

per output, 

not to exceed 

total output

current)

220VAC 

50/60Hz

Input Current

R1224DC68220

6A

12

8

P

3.5A

0.9A

24

R1224DC68CB220

12

8

P

2.5A

0.9A

24

Specifications:

Installation Instructions:

1.  Unit is factory set at 12VDC. To adjust the output voltage remove the bottom cover to access DIP switch 
 

on the power supply board (Fig. 1a, pg. 3).

2.  Mount unit in the desired rack location (Space unit at least 3” from any video monitors).
3.  Set power switch on the back of the unit to the OFF position (Fig. 1e, pg. 3).
4.  Plug power cord into a grounded 220VAC 50/60 Hz receptacle (Fig. 1d, pg. 3).
5.  Set power switch to the ON (RESET) position and measure output voltage before connecting devices 
 

(Fig. 1e, pg. 3). This helps avoiding potential damage.

6.  Set power switch on the back of the unit to the OFF position (Fig. 1e, pg. 3).
7.  Connect devices to the removable terminal blocks marked [1P & 1N] through [8P & 8N] (Fig. 1c, pg. 3).
 

When wiring is completed on terminal blocks, they can be locked down by tightening screw flanges.

 

All terminals with common suffix (P) “1P, 2P...” are the same polarity (positive).

 

All terminals with common suffix (N) “1N, 2N...” are the same polarity (negative).

8.  Upon completion of the wiring, set power switch on back of unit to the ON (RESET) position (Fig. 1e, pg. 3).
9.  Green power LEDs on faceplate will illuminate when AC power is present. When an output is in a trouble 
 

condition (blown fuse or tripped PTC), the corresponding LED will not be illuminated (Fig. 1, pg. 3).

 

a.  Blown fuse (R1224DC68220) - Set power switch on the back of the unit to the OFF position 

  (Fig. 1e, pg. 3). Remove front faceplate to access fuses. Replace with fuses rated @ 3.5A/250VA 
 

 

(Altronix model # Fuse1).

 

b.  Tripped PTC (R1224DC68CB220) - To reset PTC, set power switch on the back of unit to the OFF 

 

 

position. After approximately 30 secs. set power switch to the ON (RESET) position (Fig. 1e, pg. 3).

10.  Power switch with built-in circuit breaker:
 

OFF position - Switch not illuminated. Outputs not powered.

 

RESET (ON) position - Switch illuminated. Outputs powered.

 

Circuit breaker tripped - Switch not illuminated. Power LEDs on faceplate are not illuminated. Outputs not 

 

powered. To reset circuit breaker set power switch to the ON (RESET) position (Fig. 1e, pg. 3).

Input:

•  220VAC, 50/60Hz, 0.9A.

Output:

•  Eight (8) fuse or PTC protected outputs. 
•  12VDC or 24VDC @ 6A
  (0.75A per device, 3.5A max.)
•  Outputs are rated @ 3.5A (fused) or 2.5A (PTC).
•  Surge suppression.

Battery Backup:

•  Built-in charger for sealed lead acid or 
  gel type batteries.
•  Automatic switch over to stand-by battery when 
  AC fails.
•  Maximum charge current 0.7A.

Features:

•  Eight (8) power LEDs.
•  Illuminated master power disconnect circuit breaker
  with manual reset.
•  3-wire grounded line cord.
•  Removable terminal blocks with 
  locking screw flange.
•  Unit maintains camera synchronization.
•  Spare fuses provided.

Mechanical:

•  2U rack mount chassis for use in standard 
  EIA 19” rack.
•  Enclosure Dimensions (H x W x D approx.):
  3.26” x 19.125” x 8.5” (83mm x 486mm x 216mm)