For continuous protection against fire replace fuse with the
same type and rating 5mm - 20mm, 250V, 2A.
LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal
Legend
Function/Description
L, G, N
Connect 220VAC to these terminals: Black to Hot, White to Neutral, Green to ground.
– DC +
12VDC @ 1.0A continuous supply current. 24VDC @ 0.5A continuous supply current.
– BAT +
Stand-by battery connections. Maximum charge rate 0.3A.
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.
IIOLS20220 - Rev. 080905
B25S
MEMBER
MADE IN USA
L
G
N
---
BA
T
+
DC
PTC2
VR1
AC
---
DC
+
OFF - 24V
ON - 12V
SW1
ON
1
2A
250V