LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition.

OFF

OFF

No DC output. Loss of AC. Discharged or no battery present. 

 

Terminal Identification:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground.

– DC +

12VDC @ 10A continuous supply current. 

AC FAIL

NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. 

Relay normally energized when AC power is present. Contact rating 1A @ 28VDC.

Low Battery

NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel.

Relay normally energized when DC power is present.

Contact rating 1A @ 28VDC

Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC.

– BAT +

Stand-by battery connections. Maximum charge rate 0.7A.

LOW BA

T

NC    C   NO     NC   C     NO

AC FAIL

---  BAT  +

---  DC  +

L

G

N

5A 250V

OFF    ON

OLS200

AC

DC

Fig. 1

Altronix is not responsible for any typographical errors.

––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056

website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty

IIOLS200 - Rev. 010704 