LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal Legend
Function/Description
L, G, N
Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground.
– DC +
12VDC @ 10A continuous supply current.
AC FAIL
NC, C, NO
Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present. Contact rating 1A @ 28VDC.
Low Battery
NC, C, NO
Used to indicate low battery condition, e.g. connect to alarm panel.
Relay normally energized when DC power is present.
Contact rating 1A @ 28VDC
Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC.
– BAT +
Stand-by battery connections. Maximum charge rate 0.7A.
LOW BA
T
NC C NO NC C NO
AC FAIL
--- BAT +
--- DC +
L
G
N
5A 250V
OFF ON
OLS200
AC
DC
Fig. 1