LED Diagnostics:
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal Legend
Function/Description
L, G, N
Connect 220VAC to these terminals: L to Hot, N to Neutral, G to ground.
– DC +
12VDC / 24VDC @ 6A continuous supply current.
AC FAIL
NC, C, NO
Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present. Contact rating 1A @ 28VDC
Low Battery
NC, C, NO
Used to indicate low battery condition, e.g. connect to alarm panel.
Relay normally energized when DC power is present. Contact rating 1A @ 28VDC.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC.
24VDC output threshold set @ approximately 21VDC.
– BAT +
Stand-by battery connections. Maximum charge rate 0.7A.
--- BAT +
--- DC +
AC
OLS180220
DC
LOW BA
T
NC C NO NC C NO
AC FAIL
L
G
N
OFF ON
5A 250V
OFF - 24V
ON - 12V
ON
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty
IIOLS180220 - Rev. 010704