LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition.

OFF

OFF

No DC output. Loss of AC. Discharged or no battery present. 

 

Terminal Identification:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground.

– DC +

12VDC / 24VDC @ 6A continuous supply current. 

AC FAIL 
NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. 
Relay normally energized when AC power is present. 
Contact rating 1A @ 115VAC / 28VDC

Low Battery 
NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally 
energized when DC power is present. Contact rating 1A @ 115VAC / 28VDC.
Low battery threshold: 
 

12VDC output threshold set @ approximately 10.5VDC. 

 

24VDC output threshold set @ approximately 21VDC.

– BAT +

Stand-by battery connections. Maximum charge rate 0.7A.

Altronix is not responsible for any typographical errors.