Maximal3FV / Maximal5FV / Maximal7FV Access Power Controllers (Fused)

eFlow Power Supply/Charger:

•  Input: 220VAC (working range 198VAC - 256VAC), 50/60Hz. 

•  For output voltage and supply current refer to MaximalFV series Configuration Chart, pg. 3.

•  Auxiliary output rated @ 1A (unswitched).

•  Overvoltage Protection.

•  Built-in charger for sealed lead acid or gel type batteries.

•  Maximum charge current 1.54A.

•  Automatic switch over to stand-by battery when AC fails. 

  Transfer to stand-by battery power is instantaneous with no interruption.

•  Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open 

  (NO) or normally closed (NC) trigger.

•  AC fail supervision (form “C” contacts).

•  Battery fail and presence supervision (form “C” contacts).

•  Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units 

  and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.

•  For fuse ratings refer to MaximalFV Series Configuration Chart, pg. 3.

•  Green AC Power LED indicates 220VAC present.

•  AC input and DC output LED indicators.

•  Short circuit and overload protection.

•  Enclosure accommodates up to four (4) 12VDC/12AH batteries.

Enclosure dimensions (H x W x D): 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.8mm).

MaximalFV Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, the Canadian Electric 

Code, Part I, Part II and with all local codes and authorities having jurisdiction. Product is intended for indoor 

use only. 

 

Power Supply Board LED Diagnostics 

(pg. 6)

 

Access Power Controller LED Diagnostics 

(pg. 6)

 

Power Supply Board Terminal Identification 

(pg. 6)

 

Access Power Controller Terminal Identification 

(pg. 7)

 

Power Supply Board Stand-by Battery Specifications 

(pg. 7)

 

Power Supply Board Output Voltage Settings 

(pg. 7)

 

Access Power Controller Typical Application Diagram 

(pg. 8)

 

FACP/Optional Power Supply Hook-up Diagrams 

(pg. 11)

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top three keyholes in 

 

the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place 

 

the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position of the 

 

lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the 

 

enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to 

 

tighten all screws (Enclosure Dimensions, pg. 12).

2.  Connect unswitched AC power (220VAC 50/60Hz) to terminals marked [L, N] (Fig. 3, pg. 9). Do not use 

 

terminal marked [G]. Use 14 AWG or larger for all power connections. Secure ground wire lead to 

 

earth ground lug.

 

Keep power-limited wiring separate from non power-limited wiring. 

 

Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to 

 

qualified service personnel.

3.  Select desired DC output voltage by setting SW1 to the appropriate position on the Maximal3FV power 

 supply 

(Fig. 1a, pg. 7). Maximal5FV power supply is factory set at 12VDC and Maximal7FV power supply 

 

is factory set at 24VDC.

4.  Measure the output voltage of the unit before connecting any devices to ensure proper operation.

 

Improper or high voltage will damage these devices.

5. 

Output options (Fig. 2, pg. 8):

 

The unit will provide either sixteen (16) switched power outputs, sixteen (16) dry form “C” outputs, or any

 

combination of both switched power and form “C” outputs.

 

(a)  Fail-Safe Switched Power outputs: 

 

 

For Fail-Safe operation connect the positive (+) input of the access control devices to terminal marked 

 

 

[NC]. Connect the negative (–) input of the access control devices to terminal marked [COM].

 

(b) Fail-Secure Switched Power outputs:

 

 

For Fail-Secure operation connect the positive (+) input of the access control devices to terminal marked 

 

 

[NO]. Connect the negative (–) input of the access control devices to terminal marked [COM].

 

(c)  Form “C” outputs:

 

 

When form “C” outputs are desired, the corresponding output fuses (1-8) of each ACM8 board must 

 

 

be removed.

Содержание Maximal3FV

Страница 1: ...outputs Maximal5FV 12VDC 8 6A Sixteen 16 fuse protected outputs Maximal7FV 24VDC 9 2A Sixteen 16 fuse protected outputs Rev SFFV031115 More than just power TM Installing Company _________________ Service Rep Name _______________________________________ Address ____________________________________________________ Phone ______________________ ...

Страница 2: ... Board LED Diagnostics pg 6 Access Power Controller LED Diagnostics pg 6 Power Supply Board Terminal Identification pg 6 Access Power Controller Terminal Identification pg 7 Power Supply Board Stand by Battery Specifications pg 7 Power Supply Board Output Voltage Settings pg 7 Access Power Controller Typical Application Diagram for each ACM8 pg 8 MaximalFV Battery Hookup and Tamper Switch Installa...

Страница 3: ...C Output Range volts 24VDC Output Range volts Maximal3FV 10 0 13 2 20 19 26 4 10 03 13 2 20 19 26 4 12VDC 4 6A or 24VDC 5 2A 16 3 5 2 5 5A 250V 10A 32V 10A 250V 2 5A 250V Maximal5FV 10 03 13 2 10 03 13 2 8 6A 16 3 5 2 5 5A 250V 15A 32V 10A 250V 2 5A 250V Maximal7FV 20 17 26 4 20 28 26 4 9 2A 16 4 5 2 5 6 3A 250V 15A 32V 10A 250V 2 5A 250V MaximalFV Series Features ACM8 Access Power Controller Modu...

Страница 4: ...rill holes in the wall to line up with the top three keyholes in the enclosure Install three upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the three upper screws level and secure Mark the position of the lower three holes Remove the enclosure Drill the lower holes and install the three fasteners Place the enclosure s upper keyholes...

Страница 5: ...CM8 boards 10 Stand by Battery Connections Fig 3 pg 9 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Connect battery to terminals marked BAT Fig 3 pg 9 Use two 2 12VDC batteries connected in series for 24VDC operation battery le...

Страница 6: ...tery connection wires Note Maximum charge current is 1 54A Expected battery life is 5 years however it is recommended to change batteries within 4 years or less if necessary Power Supply Board LED Diagnostics Red DC Green AC AC1 Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by ba...

Страница 7: ...V 10 03 13 2VDC 8 6A Maximal7FV 20 17 26 4VDC 9 2A Fail Safe NC positive COM Negative Fail Secure NO positive COM Negative Auxiliary output C positive COM Negative When using AC power supplies polarity needs not to be observed NC C NO convert to dry form C 5A 24VAC VDC rated dry outputs when fuses are removed Contacts shown in a non triggered state FACP INTERFACE T INPUT Fire Alarm Interface trigg...

Страница 8: ...COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 TRG FACP INTERFACE 10A 250V FACP Dry Form C Outpu...

Страница 9: ...an fit in this enclosure An external battery enclosure must be used if using the 40AH or 65AH batteries Line Neutral Ground Lug NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET N...

Страница 10: ...ptional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply For Canadian installations use shielded wiring for all connections Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 4a External Jacketed Shield Incor...

Страница 11: ...J3 FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG J3 NO C NC FACP INTERFACE JUMPER N C DRY TRIGGER INPUT TRG J3 NO C NC FACP INTERFACE N C TRIGGER INPUT N C RESET SWITCH JUMPER TRG J3 N O TRIGGER INPUT TRG J3 NO C NC FACP INTERFACE N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG J3 NO C NC Fig 7 Normally Open FACP Latching trigger input with reset Fig 8 Normally Closed Non Latching FACP trigger input ...

Страница 12: ... 50 8mm 2 50 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 26 660 4mm 26 660 4mm 7 5 190 5mm 5 127mm 26 660 4mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8...

Отзывы: