background image

 

- 4 - 

MaximalRDV Rack Access Power Controllers (PTC)

Installation Instructions:

Important:

 

Adjust output voltages and Fire Alarm Interface configuration before installing unit in the rack .

1 .  Separate bottom and top of the rack mount chassis by removing six (6) screws 
 

(Rack Mechanical Drawing and Dimensions, pg. 12) .

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to 

 

qualified service personnel.

2 . 

Set output voltage:

 

Select desired DC output voltage by setting SW1 on the power supply board(s) (Fig. 1a, pg. 6) to the 

 

appropriate position (Output Voltage and Stand-by Specification Charts, pg. 5) . 

 

For Maximal33RDV each set of eight (8) outputs can be set for 12VDC or 24VDC 

 

(example: eight (8) outputs @ 12VDC and eight (8) outputs @ 24VDC) .

3 . 

Input trigger programming options:

 

The unit can be programmed to operate with either a normally open or normally closed input from access 

 

control devices by setting switches SW3 on either the ACM8CBR-S or ACM16CBR-S board to the 

 

appropriate position (Fig. 2b, pg. 7); OFF for a normally closed [NC] trigger input or ON for a normally 

 

open [NO] input .

4 . 

Output programming options:

 

a .  The outputs can be programmed to be either all Fail-Safe (i .e . mag locks), all Fail-Secure (i .e . electric 

 

 

strikes) or any combination of each by setting the corresponding OUTPUT SELECT dip switches (1-8) 

 

 

on the ACM8CBR-S board to the appropriate position; ON for Fail-Safe outputs or OFF for Fail-Secure 

   outputs 

(Fig. 2a, pg. 7) . 

  

Note: the output configuration will follow the input trigger option

 

b .  To enable the FACP Disconnect for an output the corresponding FIRE ALARM INTERFACE switch 

 

 

must be in the ON position . To disable the FACP Disconnect the FIRE ALARM INTERFACE dip 

 

 

switches (1-8) on the ACM8CBR-S/ACM16CBR-S board must be in the OFF position (Fig. 2a, pg. 7) .

5 . 

Fire Alarm Interface hookup options:

 

A normally closed [NC], normally open [NO] input or polarity reversal from an FACP signaling circuit 

 

will trigger the selected outputs (Figs. 6-11, pg. 9) . To program the Fire Alarm Interface set dip switches 

 

SW1 and SW2 on the ACM8CBR-M board to the appropriate positions (Figs. 3a and 3b, pg. 7) 

 

(Fire Alarm Interface Switch Settings pg. 5) .

6 . 

Battery Connections:

 

For access control applications batteries are optional . If batteries are not used, a loss of AC will result in 

 

the loss of output voltage . When batteries are used, they must be lead acid or gel type . Connect one (1) 

 

battery to the terminals marked [– BAT +] for 12VDC operation . Use two (2) 12VDC batteries wired in 

 

series for 24VDC operation (Fig. 4b, 5b, pg. 8) . The rack mount enclosure will not accommodate batteries . 

 

A separate battery enclosure is required . 

 

Note: When using the Maximal33RDV with battery backup, two (2) separate batteries or sets of batteries 

 

must be used .

7 . 

Battery and AC Supervision outputs:

 

Connect the appropriate notification signaling device to the terminals marked AC Fail and Battery Fail on 

 

the power supply board(s) (Fig. 4a/5a, pg. 8) . 

 

Use 22AWG to 18AWG for AC Fail and Low/No Battery reporting .

8 .  Reassemble the bottom and top of the rack mount chassis by fastening the six (6) screws . 
 

(Rack Mechanical Drawing and Dimensions pg. 12) .

9 .  Attach mounting brackets to the rack mount Maximal for desired rack or wall installation (Fig. 12-14, pg. 10) .
10 .  Mount in the desired rack location . Do not obstruct side air vents .
11 .  Set the power disconnect circuit breaker to the OFF position (Fig. 15a, pg. 12).
12 .  Plug power cord into a grounded 220VAC 50/60Hz receptacle (Fig. 15b, pg. 12) .
13 .  Set the power disconnect circuit breaker to the ON position (Fig. 15a, pg. 12).
14 .  Measure the output voltage before connecting devices . This helps avoiding potential damage .
15 .  Set the power disconnect circuit breaker to the OFF position (Fig. 15a, pg. 12).
16 . 

Input trigger connections:

 

Connect the Normally Open or Normally Closed input triggers from the access control devices to the 

 

removable terminals marked [IN1 and GND] through [IN8 and GND] for Maximal1RHDV and 

 

Maximal3RHDV . For Maximal1RDV, Maximal3RDV and Maximal33RDV connect devices to the second 

 

set of terminals marked [IN1 and GND] through [IN8 and GND] . Make sure the devices match settings of 

 

SW3 in step 3 (Rack Mechanical Drawing and Dimensions pg. 12) .

17 . 

Output connections:

 

Connect the devices to be powered to the removable terminals marked [– OUT1 +] to [– OUT8 +] for 

 

Maximal1RHDV and Maximal3RHDV . For Maximal1RDV, Maximal3RDV and Maximal33RDV connect 

 

devices to the second set of terminals marked [– OUT1 +] to [– OUT8 +] (Fig. 15c, pg. 12) .

Содержание Maximal1RDV

Страница 1: ...al1RDV 12VDC 4A or 24VDC 3A 12VDC 4A or 24VDC 3A Eight 8 PTC Protected Outputs Sixteen 16 PTC Protected Outputs Maximal3RHDV Maximal3RDV 12VDC or 24VDC 6A 12VDC or 24VDC 6A Eight 8 PTC Protected Outpu...

Страница 2: ...tion Charts pg 5 LED Diagnostics pg 5 Power Supply Board Output Voltage Settings pg 6 Fire Alarm Interface Output Selection and Input Type pg 7 Power Supply Boards Drawings pg 8 FACP Hook Up Diagrams...

Страница 3: ...Maximal3RHDV 12VDC 6A N A 6A 8 2 0A 0 9A 3 5A 250V 24VDC 6A N A Maximal3RDV 12VDC 6A N A 6A 16 2 0A 0 9A 3 5A 250V 24VDC 6A Maximal33RDV 12VDC 6A 12VDC 6A 12A 16 2 0A 1 9A 3 5A 250V 24VDC 6A 24VDC 6A...

Страница 4: ...to the appropriate positions Figs 3a and 3b pg 7 Fire Alarm Interface Switch Settings pg 5 6 Battery Connections For access control applications batteries are optional If batteries are not used a loss...

Страница 5: ...is fully charged check specified voltage at the battery terminals and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Fire Alarm Interface Switch Se...

Страница 6: ...enclosure that may be of sufficient magnitude to constitute an electric shock The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating...

Страница 7: ...OUTPUT SELECT ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 FIRE ALARM INTERFACE OUTPUT SELECT ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 INPUT TYPE SW3 SW3 DIP Switch for NO or NC Input ON...

Страница 8: ...y and AC Supervision LOW BAT NC C NO NC C NO AC FAIL ON Power Supply Board Maximal1RHDV Maximal1RDV Fig 4 BAT Built in Battery Charging Power Supply Board L G N 5A 250V Built in Battery Charging Batte...

Страница 9: ...set Switch 1 2 FACP RESET Fig 7 Latching Latching Latching Normally Closed Input from FACP GND IN8 GND Factory Installed Jumper Normally Closed NC Dry Trigger Input 1 2 FACP RESET 1 2 GND FACP IN8 RES...

Страница 10: ...head screws B to secure brackets 3 Carefully place faceplate over LEDs and secure using three 3 pan head screws C on top and three 3 pan head screws C on the bottom of faceplate Fig 13b 4 Slide unit...

Страница 11: ...MaximalRDV Rack Access Power Controllers PTC 11 Notes...

Страница 12: ...19 125 x 8 5 82 6mm x 485 8mm x 215 9mm 3 125 79 4mm 8 5 215 9mm 0 75 19 1mm 19 125 485 8mm 17 625 447 7mm OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 2 1 OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15 OUT16 I...

Отзывы: