Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
 

FACP Supervision: 

To ensure proper connection and operation of the Fire Alarm disconnect 

 

 

hookup . Please follow the appropriate procedure below:

 

Normally Open Input: 

Placing a short between terminals marked [T] and [+ INP] will trigger the 

 

 

Fire Alarm Disconnect . Remove the short to reset .

 

Normally Closed Input: 

Remove the wire from terminal marked [INP –] will trigger the Fire Alarm 

 

 

Disconnect . Replace the wire to terminal marked [INP –] to reset .

 

FACP Signal Circuit Input:  It is necessary to trigger the Fire Alarm System .

 

 

In all of the above scenarios the green TRG LED of the ACM8s will 

 

 

illuminate . All outputs selected for Fire Alarm Disconnect will activate 

 

 

releasing locking devices .

  

Note: All outputs [OUT 1 - OUT 8] must be in a normal (de-energized) 

 

 

condition prior to testing . When the unit is configured for Normally Open 

  

(Fig. 13, pg. 18) or Normally Closed (Fig. 15, pg. 18) latching operation, 

 

 

it is necessary to reset the Fire Alarm Disconnect by activating the 

 

 

Normally Closed reset switch .

 

Output Voltage Test: 

Under normal load conditions, the DC output voltage should be checked 

 

 

for proper voltage level (Power Supply Board Stand-by Battery 

 

 

Specifications, pg. 8).

 

Battery Test: 

Under normal load conditions check that the battery is fully charged, check 

 

 

specified voltage at the battery terminals and at the board terminals marked 

 

 

[+ BAT –] to ensure that there is no break in the battery connection wires .

  

Note: AL400XB2V, AL600XB220 and AL1012XB220 Power Supply 

  

Board 

maximum charge current is 0 .7A . 

  

AL1024XB2V Power Supply Board maximum charge current is 3 .6A .

 

 

Expected battery life is 5 years; however, it is recommended to change 

 

 

batteries within 4 years or less if necessary .

Power Supply Board LED Diagnostics:

LED

Power Supply Status

Red (DC)

Green (AC)

ON

ON

Normal operating condition .

ON

OFF

Loss of AC . Stand-by battery supplying power .

OFF

ON

No DC output . Short circuit or thermal overload condition .

OFF

OFF

No DC output . Loss of AC . Discharged battery .

Red (Bat)

Battery Status

ON

Normal operating condition .

OFF

Battery fail/low battery .

Access Power Controller LED Diagnostics:

LED

ON

OFF

LED 1- LED 8 (Red) Output relay(s) energized .

Output relay(s) de-energized .

Trg (Green)

FACP input triggered (alarm condition) .

FACP normal (non-alarm condition) .

Содержание Maximal11V

Страница 1: ...uts Maximal33V Power Supply 1 12VDC 5 5A or 24VDC 5 7A Power Supply 2 12VDC 5 5A or 24VDC 5 7A Sixteen 16 fuse protected outputs Maximal55V Power Supply 1 12VDC 9 5A Power Supply 2 12VDC 9 5A Sixteen 16 fuse protected outputs Maximal77V Power Supply 1 24VDC 9 7A Power Supply 2 24VDC 9 7A Sixteen 16 fuse protected outputs Maximal75V Power Supply 1 12VDC 9 5A Power Supply 2 24VDC 9 7A Sixteen 16 fus...

Страница 2: ...ery Specifications pg 8 Power Supply Board Output Voltage Settings pg 9 Access Power Controller Typical Application Diagram for each ACM8 pg 9 Maximal11V Maximal33V Maximal55V Battery Hookup and Tamper Switch Installation pg 10 Maximal77V Battery Hookup and Tamper Switch Installation pg 11 Maximal75V Battery Hookup and Tamper Switch Installation pg 12 NEC Power Limited Wiring Requirements for Maxi...

Страница 3: ... 7A 11 2A Maximal55V AL1012XB220 AL1012XB220 19 2 6A 15A 32V 12VDC 9 5A 12VDC 9 5A Maximal75V AL1012XB220 AL1024XB2V 19 2 3 8A 15A 32V 12VDC 9 5A 24VDC 9 5A Maximal77V AL1024XB2V AL1024XB2V 19 4 5A 15A 32V 24VDC 9 7A 24VDC 9 7A MaximalV Series Features Sixteen 16 independently trigger controlled outputs Output options a Sixteen 16 Fail Safe filtered and electronically regulated power outputs b Six...

Страница 4: ...ver the three upper screws Install the three lower screws and make sure to tighten all screws Enclosure Dimensions pg 20 2 The power supply is pre wired to the ground chassis Connect main incoming ground to the provided earth safety ground lug Connect unswitched AC power 220VAC 50 60Hz to the terminals marked L N on both power supply boards Use 14 AWG or larger for all power connections Keep power...

Страница 5: ... switch upon a fire alarm input trigger to the ACM8 boards 10 Stand by Battery Connections Figs 3 5 pgs 10 12 For Access Control applications batteries are optional If batteries are not used a loss of AC will result in the loss of output voltage Batteries must be lead acid or gel type Connect one 1 12VDC battery to the terminals marked BAT for 12VDC operation Figs 3 5 pgs 10 12 Use two 2 12VDC bat...

Страница 6: ...m Disconnect by activating the Normally Closed reset switch Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level Power Supply Board Stand by Battery Specifications pg 8 Battery Test Under normal load conditions check that the battery is fully charged check specified voltage at the battery terminals and at the board terminals marked BAT t...

Страница 7: ...AT for 12VDC operation Fig 3 pg 10 Fig 5 pg 12 Use two 2 12VDC batteries wired in series for 24VDC operation Figs 3 5 pgs 10 12 Access Power Controller Terminal Identification Terminal Legend Function Description Power 12VDC or 24VDC input from power supply board Control only applicable for Maximal11 These terminals can be connected to an external access control power supply to provide isolated op...

Страница 8: ...ion 12VDC 40AH N A 3 5A 0 5A 24VDC 40AH N A 2 7A 0 7A Maximal33 AL600XB220 Refer to Fig 1a pg 9 for Switch SW1 location and position 12VDC 40AH N A 5 5A 5 5A 24VDC 40AH N A 5 5A 0 7A Maximal55 Maximal75 AL1012XB220 Factory set at 12VDC 12VDC 12AH 9 0A Battery capacity for emergency stand by at least 20 min N A Maximal75 AL1024XB2V Factory set at 24VDC 24VDC 12AH 7 7A 1 2A N A Maximal77 AL1024XB2V ...

Страница 9: ...ed Power Supply For this application corresponding fuse F8 must be removed Keypad NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 ...

Страница 10: ...TPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM ...

Страница 11: ...ED6 LED7 LED8 J2 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5...

Страница 12: ...C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N NC C NO COM OUTPUT 1 LED1 F1 N...

Страница 13: ...ent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 6a External Jacketed Shield Incorrect Wire Handling Cor...

Страница 14: ...cific application may require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 7a External Jackete...

Страница 15: ...ent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 8a External Jacketed Shield Incorrect Wire Handling Cor...

Страница 16: ...ent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 9a External Jacketed Shield Incorrect Wire Handling Cor...

Страница 17: ... POWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER Fig 10 Optional hook up using two 2 isolated power supply inputs Only applicable on Maximal11V CUT JUMPER FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG NO C NC FACP INTERFACE Fig 11 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition Fig 12 Normally Open Non Latching FACP trigger input N O TRIGGER INPUT TRG...

Страница 18: ...nt d N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC Fig 13 Normally Open FACP Latching trigger input with reset JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 14 Normally Closed Non Latching FACP trigger input N C TRIGGER INPUT N C RESET SWITCH JUMPER TRG Fig 15 Normally Closed Latching FACP trigger input with reset ...

Страница 19: ...Maximal11V Maximal33V Maximal55V Maximal77V Maximal75V Access Power Controllers Fused 19 Notes ...

Страница 20: ...0 8mm 2 50 8mm 2 50 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 26 660 4mm 26 660 4mm 7 5 190 5mm 5 127mm 26 660 4mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 71...

Отзывы: