MaxiFit11E/13E/33E/35E/37E/55E/75E/77E Expandable Power Systems Installation Guide 

- 5 -

Power Supply Board LED Diagnostics:

LED

Power Supply Status

Red (DC)

Green (AC)

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition.

OFF

OFF

No DC output. Loss of AC. Discharged battery.

Red (Bat)

Battery Status

ON

Normal operating condition.

OFF

Battery fail/low battery.

Terminal Identification:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals: L to hot, N to neutral 

(Fig. 1a, pg. 4)

.

+ DC – **

Refer to MaxFit E Series Configuration Chart, pg 2.

AC FAIL

NO, C, NC

Used to notify loss of AC power, e.g.connect to audible device or alarm panel. 

Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. 

AC or brownout fail is reported within 1 minute of event. 

To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit 

(Fig. 1b, pg. 4)

.

BAT FAIL

NO, C, NC

Used to indicate low battery condition, e.g. connect to alarm panel. 

Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. 

A removed battery is reported within 1 minute. 

Battery reconnection is reported within 1 minute.

Low battery threshold: approximately 21VDC 

(Fig. 1b, pg. 4)

.

+ BAT – ***

Stand-by battery connections 

(Fig. 1c, pg. 4)

.

MaxFit3E and MaxFit5E maximum charge current 0.7A.

MaxFit7E maximum charge current 3.6A.

**  AL1012ULXB terminals marked [– DC +]

***  AL1024ULXB2 terminals marked [– BAT +]

Содержание MAXIMAL FIT MaxFit E Series

Страница 1: ...VDC 4A or 24VDC 3A Power Supply 2 12VDC 4A or 24VDC 3A MaxFit13E Power Supply 1 12VDC or 24VDC 6A Power Supply 2 12VDC 4A or 24VDC 3A MaxFit33E Power Supply 1 12VDC or 24VDC 6A Power Supply 2 12VDC or...

Страница 2: ...12VDC 6A 12VDC 6A 12VDC 6A 24VDC 6A 24VDC 6A 24VDC 6A MaxFit35E AL1012ULXB AL600ULXB 2 6 1A 5A 250V 15A 32V AL1012ULXB 12VDC 10A 12VDC 6A 12VDC 10A 24VDC 6A MaxFit37E AL1024ULXB2 AL600ULXB 2 7 9A 5A...

Страница 3: ...ls marked L N Fig 1a pg 5 Use 14 AWG or larger for all power connections Secure green wire lead to earth ground For Fire Alarm applications the outputs are Special Applications only Keep power limited...

Страница 4: ...Test Under normal load conditions check that the battery is fully charged check specified voltage at the battery terminals and at the board terminals marked BAT to ensure that there is no break in the...

Страница 5: ...rt pg 2 AC FAIL NO C NC Used to notify loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1A 28VDC AC or brownout fail is re...

Страница 6: ...C 12AH N A 200mA N A N A 24VDC 40AH N A 3A 1A 300mA MaxFit13E MaxFit33E MaxFit35E MaxFit37E AL600ULXB Refer to Fig 2a on pg 4 for Switch SW1 location and position 12VDC 40AH N A 6A 1A 300mA 24VDC 12AH...

Страница 7: ...tWaySP3B NetWay4EB NetWaySP4B NetWaySP8B Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries are required for ULC S319 installations CAUTION When power supply board is set...

Страница 8: ...8mm 8 75 222 3mm 8 75 222 3mm 1 50 38 1mm 1 50 38 1mm 6 25 158 8mm 1 25 31 8mm 1 25 31 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 1 25 31 8mm 1 25 31 8mm 16 50 419 1mm 1 25 31 8mm 0 75 1...

Отзывы: