LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition or defective unit.

OFF

OFF

No DC output. Loss of AC. Discharged or no battery present. 

Terminal Identification:

Terminal Legend

Function/Description

AC/AC

Low voltage AC input (see 

Voltage Output/Transformer Selection Table

). 

For 12VDC output use 16VAC with 56VA power rating or higher.

For 24VDC output use 28VAC with 85VA power rating or higher. 

– DC +

12VDC or 24VDC @ 2.5A continuous output.

– BAT +

Stand-by battery connections. Maximum charge rate 500mA.

AC FAIL

NC, C, NO

(LPS3R only)

Indicates loss of AC (e.g. connect to audible device or alarm panel).

Relay is normally energized when AC power is present.

Contact rating 1A @ 120VAC / 28VDC.

Fig. 1

AC

DC

AC

AC

--  

DC  

+
-- 

BAT 

+

NC     C    NO

SW1

12V-ON

24V-OFF

ON

SW2

12V-ON

24V-OFF

ON

ON

OFF - 24V

ON - 12V

Fig. 1b

Fig. 1a

AC

DC

AC

AC

--  

DC  

+
-- 

BAT 

+

NC     C    NO

SW1

12V-ON

24V-OFF

ON

SW2

12V-ON

24V-OFF

ON

AC

DC

AC

AC

--  

DC  

+
-- 

BAT 

+

NC     C    NO

SW1

12V-ON

24V-OFF

ON

SW2

12V-ON

24V-OFF

ON

Altronix is not responsible for any typographical errors.

––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056

website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty 

IILPS3/LPS3R - Rev. 081004 J28U

MEMBER

LPS3R only

Отзывы: