eFlowNBV Power Supply/Chargers Installation Guide

Wiring:

Use 18 AWG or larger for all low voltage power connections .

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery)

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

  Under normal load conditions, the DC output voltage should be checked for 

 

proper voltage level .

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage (12VDC @ 13 .2 or 24VDC @ 26 .4) both at the battery terminal and at the 

 

board terminals marked [– BAT +] to ensure that there is no break in the battery 

 

connection wires .

Replacing Batteries:

  Disconnect existing batteries . Connect battery to the terminals marked [– BAT +] .

 

Use two (2) 12VDC batteries connected in series for 24VDC operation .

LED Diagnostics:

Red (DC)

Clear (AC1) / Green (AC) Power Supply Status

ON

ON

Normal operating condition .

ON

OFF

Loss of AC . Stand-by battery is supplying power .

OFF

ON

No DC output .

OFF

OFF

Loss of AC . Discharged or no stand-by battery . No DC output .

Terminal Identification:

Terminal

Legend

Function/Description

L, G, N

Connect 220VAC, 50/60Hz to these terminals: L to hot, N to neutral, 

G to ground 

(Fig. 1a, pg. 5)

 .

– DC +

(Fig. 1h, pg. 5)

eFlow3NBV:

 

12VDC or 24VDC @ 2A continuous output (power-limited output) .

eFlow4NBV:

 

12VDC or 24VDC @ 4A continuous output (power-limited output) .

eFlow6NBV:

 

12VDC or 24VDC @ 6A continuous output (non power-limited output) .

eFlow102NBV:

  12VDC @ 10A continuous output (non power-limited output) .

eFlow104NBV:

  24VDC @ 10A continuous output (non power-limited output) .

Trigger EOL

Supervised

Fire Alarm Interface trigger input from a short or FACP . Trigger inputs can be normally open,

normally closed from an FACP output circuit (power-limited input) 

(Fig. 1d, pg. 5)

 .

NO, GND

RESET

FACP interface latching or non-latching (power-limited output) 

(Fig. 1c, pg. 5)

 .

+ AUX –

Auxiliary Power-Limited output rated @ 1A (unswitched) (power-limited output) 

(Fig. 1f, pg. 5)

 .

AC Fail 

NC, C, NO

Indicates loss of AC power, e .g . connect to audible device or alarm panel . 

Relay normally energized when AC power is present . 

Contact rating 1A @ 30VDC (power-limited) 

(Fig. 1b, pg. 5)

 .

Bat Fail

NC, C, NO

Indicates low battery condition, e .g . connect to alarm panel . 

Relay normally energized when DC power is present . Contact rating 1A @ 30VDC . 

A removed battery is reported within 5 minutes .

Battery reconnection is reported within 1 minute (power-limited) 

(Fig. 1b, pg. 5)

 .

– BAT +

Stand-by battery connections . Maximum charge current 1 .54A (non power-limited) 

(Fig. 1g, pg. 5)

 .

Содержание eFlowNBV Series

Страница 1: ...er Supply Charger Boards Models Include Installation Guide Rev EFNBV 061418 More than just power TM eFlow3NBV 12 or 24VDC 2A eFlow4NBV 12 or 24VDC 4A eFlow6NBV 12 or 24VDC 6A eFlow102NBV 12VDC 10A eFl...

Страница 2: ...nts Overview pg 3 Specifications pg 3 Features pg 3 Stand by Specifications pg 4 Installation Instructions pg 5 eFlowNBV configuration pg 5 Wiring pg 6 Maintenance pg 6 LED Diagnostics pg 6 Terminal I...

Страница 3: ...uts Battery Backup Built in charger for sealed lead acid or gel type batteries Automatic switch over to stand by battery when AC fails Transfer to stand by battery power is instantaneous with no inter...

Страница 4: ...Battery Burg Applications 4 hr Stand by 15 min Alarm Fire Applications 24 hr Stand by 5 min Alarm Access Control Applications Stand by 7AH 0 4A 6A 10 Mins 6A 12AH 1A 6A 0 3A 6A 35 Mins 6A 40AH 6A 6A 1...

Страница 5: ...g 5 For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm Interface Connect device to terminals marked AUX Fig 1f pg 5 6 For Access Control application...

Страница 6: ...nect 220VAC 50 60Hz to these terminals L to hot N to neutral G to ground Fig 1a pg 5 DC Fig 1h pg 5 eFlow3NBV 12VDC or 24VDC 2A continuous output power limited output eFlow4NBV 12VDC or 24VDC 4A conti...

Страница 7: ...Guide 7 Notes Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix co...

Страница 8: ...al or remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change...

Отзывы: