Altronix eFlow3NB Скачать руководство пользователя страница 2

 

- 2 - 

eFlow3NB

Overview:

Altronix eFlow3NB power supply/charger converts a 120VAC / 60Hz input to a 12VDC or 24VDC @ 2A output

Specifications:

Stand-by Specifications:

Battery

Burg. Applications

4 hr. Stand-by/15 min. Alarm

Fire Applications

24 hr. Stand-by/5 min. Alarm

Access Control

ApplicationsStand-by

7AH

0.4A/2A

N/A

1.5 Hours/2A

12AH

1A/2A

0.3A/2A

3.5 Hours/2A

40AH

2A/2A

1.2A/2A

Over 4 Hours/2A

65AH

2A/2A

1.5A/2A

Over 4 Hours/2A

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, the Canadian

Electrical Code and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 

1.  Mount the eFlow3NB in desired location/enclosure. 

2.  Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board 

 

(Fig. 1i, pg. 3)

3.  Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, G, N] (Fig. 1a, pg. 3). Use 14 AWG 

 

or larger for all power connections. Secure green wire lead to earth ground.

 

Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input, Battery 

 

Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts.

 

Shut branch circuit power before installing or servicing equipment. 

 

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

4.  Measure output voltage before connecting devices. This helps avoiding potential damage.

5.  Connect devices to be powered to terminals marked [– DC +] (Fig. 1h, pg. 3).

 

For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm 

 

Interface. Connect device to terminals marked [+ AUX –] (Fig. 1f, pg. 3).

6.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in

 

the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

 

Connect battery to terminals marked [– BAT +] (Fig. 1g, pg. 3). Use two (2) 12VDC batteries connected in 

 

series for 24VDC operation (battery leads included). 

 

Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 

 

(12V/65AH) batteries or UL recognized BAZR2 batteries of an appropriate rating.

7.  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 3) supervisory

 

relay outputs.

Agency Listings:

•  UL Recognized component for: 

 

UL294 

Access Control.

 

UL603 

Power Supplies for Use with 

    

Burglar Alarm Systems.

 

UL 1481  

Power Supplies for Fire Protective 

    

Signaling  Systems.

•  cUL Recognized:

 

ULC-S318-96  Power Supply for Burglar 

    

Alarm  Systems.

Input Rating:

•  Input 120VAC 60Hz, 3.5A.

Output:

•  Class 2 Rated power-limited output.

•  12VDC or 24VDC selectable output. 

•  2A continuous supply current. 

•  Aux. Class 2 Rated power-limited output 

  rated @ 1A (unswitched).

•  Overvoltage protection.

•  Filtered and electronically regulated outputs.

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Maximum charge current 1.54A.

Battery Backup 

(cont’d)

:

•  Automatic switch over to stand-by battery 

  when AC fails.

  Transfer to stand-by battery power is instantaneous 

  with no interruption.

Fire Alarm Disconnect:

•  Supervised Fire Alarm disconnect (latching or non-

  latching) 10K EOL resistor. Operates on a normally 

  open (NO) or normally closed (NC) trigger.

Supervision:

•  AC fail supervision (form “C” contacts).

•  Battery fail and presence supervision 

  (form “C” contacts).

•  Low power shutdown. Shuts down DC output 

  terminals if battery voltage drops below 80% of 

  nominal. Prevents deep battery discharge.

Visual Indicators:

•  Green AC Power LED indicates 120VAC present.

•  AC input and DC output LED indicators.

Additional Features:

•  Short circuit and overload protection.

Board Dimensions 

(approximate L x W x H)

:

7.5” x 4.6” x 1.75” (190.5 mm x 116.8 mm x 44.5 mm)