5.   For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in 

the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. 

Connect battery to terminals marked [-- BAT + ] (Fig. 1g, pg. 3). Use one (1) 12VDC battery. Use batteries - Casil 

CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL 

recognized BAZR2 batteries of an appropriate rating. 

6.   Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 3) supervisory relay outputs. 

7.   To delay AC reporting for 2 hrs., set SW2 to appropriate dip switch position [AC Delay] (Fig. 1c, pg. 3)

8.   To enable or disable Fire Alarm Disconnect set SW2 to appropriate dip switch position [Shutdown] (Fig. 1c, pg. 3)

9.   A short or NO or NC input triggers FACP [Trigger EOL Shutdown] (Fig. 1d, pg. 3)

10.  Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching 

[Trigger EOL Shutdown] (Fig. 1e, pg. 3)

Wiring: 

Use 18 AWG or larger for all low voltage power connections. 

Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery) 

Maintenance: 

Unit should be tested at least once a year for the proper operation as follows: 

Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level. 

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage 

(12VDC @ 13.2) both at battery terminal and at the board terminals marked [-- BAT + ] to ensure 

there is no break in the battery connection wires. 

Note: Maximum charging current under discharges is 1.54A. 

Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed. 

LED Diagnostics: 

Green (DC) 

Green (AC/AC1) 

Power Supply Status 

ON 

ON 

Normal operating condition. 

ON 

OFF 

Loss of AC. Stand-by battery supplying power. 

OFF 

ON 

No DC output. 

OFF 

OFF 

Loss of AC. Discharged or no stand-by battery. No DC output. 

Terminal Identification: 

Terminal 

Legend 

Function/Description 

L, G, N 

Connect 120VAC 60Hz to these terminals: L to hot, N to neutral, G to ground (non power-limited) 
(Fig. 1a, pg. 3)

-- DC + 

12VDC @ 10A continuous output (Fig. 1h, pg. 3)

Trigger EOL 

Supervised 

Fire Alarm Interface trigger input from a short or FACP.  Trigger inputs can be normally open, 

normally closed from an FACP output circuit (Power-Limited input) (Fig. 1d, pg. 3)

NO, GND 

RESET 

FACP interface latching or non-latching (Power-Limited) (Fig. 1c, pg. 3)

+ AUX ­ -

Auxiliary Power-Limited output rated @ 1A (unswitched) (Power-Limited output) (Fig. 1f, pg. 3)

AC Fail 

NC, C, NO 

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized 

when AC power is present. Contact rating 1A @ 30VDC (Power-Limited) (Fig. 1b, pg. 3)

Bat Fail 

NC, C, NO 

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power 

is present. Contact rating 1A @ 30VDC. A removed battery is reported within 5 minutes. 

Battery reconnection is reported within 1 minute (Power-Limited) (Fig. 1b, pg. 3)

-- BAT + 

Stand-by battery connections. Maximum charge current 1.54A (non power-limited) (Fig. 1g, pg. 3)