eFlowNA8V Series 

- 5 -

 

(c)  Form “C” outputs:

 

 

When form “C” outputs are desired, the corresponding output fuses (1-8) of each ACM8 board must 

 

 

be removed.

6. 

ACM8 Auxiliary Power outputs (unswitched):

 

Connect access control devices that require constant power to terminals marked [C] positive (+) and [COM] 

 

negative (–). Outputs can be used to provide power for card readers, keypads etc.

 

eFlowV Auxiliary outputs (unswitched):

 

For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm 

 

Interface. Connect device to terminals marked [+ AUX –] (Fig. 3, pg. 9).

7. 

Input trigger options (Fig. 2, pg. 8):

 

(a)  Normally Open [NO] input trigger:

 

 

Inputs 1-8 are activated by normally open or open collector sink inputs. Connect access control panel 

 

 

outputs, keypads, push buttons, REX PIRs, etc. to terminals marked [IN] and [GND]. 

 

(b) Open Collector Sink inputs:

 

 

Connect the access control panel open collector sink positive (+) to terminals marked [IN] and the 

 

 

negative (–) to terminals marked [GND].

8. 

ACM8 Fire Alarm Interface options (Figs. 5-10, pg. 11-12)

 

A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity 

 

reversal input from an FACP signaling circuit will affect selected outputs. To enable FACP Disconnect for 

 

an output turn the corresponding switch(es) [SW1-SW8] OFF on each ACM8 board. To disable FACP 

 

disconnect for an output turn the corresponding switch(es) [SW1-SW8] ON on each ACM8 board.

 

(a)  Normally Open [NO] input:

 

 

For non-latching hook-up refer to (Fig. 7, pg. 11). For latching hook-up refer to Fig. 8, pg. 12.

 

(b) Normally Closed [NC] input:

 

 

For non-latching hook-up refer to (Fig. 9, pg. 12). For latching hook-up refer to Fig. 10, pg. 12.

 

(c)  FACP Signaling Circuit input trigger:

 

 

Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals 

 

 

marked [+ INP –]. Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced 

 

 

in an alarm condition). Jumper located next to TRG LED must be cut (Fig. 6, pg. 11)

9. 

FACP Dry form “C” output (Fig. 2b, pg. 8):

 

Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C] 

 

FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.

10. 

Stand-by Battery Connections (Fig. 3, pg. 9):

 

For U.S. Access Control applications batteries are optional. Batteries are required for Canadian installations 

 

(ULC-S319). When batteries are not used, a loss of AC will result in the loss of output voltage. 

 

When the use of stand-by batteries is desired, they must be lead acid or gel type.

 

Connect battery to terminals marked [– BAT + ] (Fig. 3, pg. 9). Use two (2) 12VDC batteries connected in 

 

series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), 

 

CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 

 

and BAZR8 batteries of an appropriate rating. 

11. 

Battery and AC Supervision outputs (Fig. 3, pg. 9):

 

It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT Fail] 

 

supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices. 

 

Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting.

12.  To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Fig. 3, pg. 9).
 

To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Fig. 3, pg. 9).

13.

  Fire Alarm Disconnect (Fig. 3, pg. 9):

 

To enable Fire Alarm Disconnect set dip switch [Shutdown] to ON position.

 

To disable Fire Alarm Disconnect set dip switch [Shutdown] to OFF position.

14. 

Installation of tamper switch (Fig. 3a, pg. 9):

 

Mount UL Listed tamper switch (Altronix Model TS112 or equivalent) at the top of the enclosure. Slide the 

 

tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 3a, pg. 9).

 

Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting 

 

device. To activate alarm signal open the door of the enclosure.

15. 

Multiple power supply inputs (Fig. 2, pg. 8):

 

When using an additional Listed external power supply, jumpers J1 and J2 located on corresponding ACM8 

 

board must be cut (Fig. 2c, 2d, pg. 8 and Fig. 5, pg. 11). Connect external Listed power-limited access 

 

control power supply to the terminals marked [– C] (These terminals are paralleled to the [– Power +] 

 

terminals). When using DC power supplies, polarity must be observed. When using AC power supplies, 

 

polarity needs not be observed (Fig. 2d, pg. 8). All field wiring connections must be made employing 

 

suitable gauge CM or FPL jacketed wire (or equivalent substitute) (Fig. 4a, pg. 10).

Содержание eFlow102NA8V

Страница 1: ...eFlow102NA8V eFlow104NA8V 10A 12VDC 10A 24VDC Eight 8 Fused Outputs Eight 8 Fused Outputs For a red enclosure add an R suffix to the part e g eFlow4NA8VR Rev eFlowNA8V062717 More than just power TM In...

Страница 2: ...y Battery Specifications pg 8 Power Supply Board Output Voltage Settings pg 8 Access Power Controller Typical Application Diagram ACM8 pg 8 NEC Power Limited Wiring Requirements for eFlowNA8V Models p...

Страница 3: ...battery and it is suitable to power sensors electro mechanical devices e g electric door strikes eFlow6NA8V eFlow102NA8V and eFlow104NA8V The DC output for these power supplies are not power limited...

Страница 4: ...rews Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pg 16 2 Connect AC circuit 220VAC 50 60Hz as follows Green branch wire connects to earth safety ground Line a...

Страница 5: ...CP for normally closed output 10 Stand by Battery Connections Fig 3 pg 9 For U S Access Control applications batteries are optional Batteries are required for Canadian installations ULC S319 When batt...

Страница 6: ...terminal marked INP to reset FACP Signal Circuit Input It is necessary to trigger the Fire Alarm System In all of the above scenarios the green TRG LED of the ACM8 will illuminate All outputs selected...

Страница 7: ...l Identification Terminal Legend Function Description Power 12VDC or 24VDC from power supply charger factory connected These terminals are paralleled to the Control terminals Control These terminals a...

Страница 8: ...romagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Keypa...

Страница 9: ...ted for all other models Fire Alarm Interface power limited Inputs power limited J2 F8 J1 J3 1 2 3 4 O N 1 2 3 4 O N Ground Lug Unswitched 220VAC power mains Non power limited Battery Connections non...

Страница 10: ...ections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring meth...

Страница 11: ...ig 5 Optional hook up using two 2 isolated power supply inputs Only applicable on eFlow4NA8V Fig 6 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition...

Страница 12: ...r input with reset Fig 9 Normally Closed Non Latching FACP trigger input Fig 10 Normally Closed Latching FACP trigger input with reset N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC JUMPER N C...

Страница 13: ...rol of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state cha...

Страница 14: ...14 eFlowNA8V Series Notes...

Страница 15: ...eFlowNA8V Series 15 Notes...

Страница 16: ...38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm...

Отзывы: