NEC Power-Limited Wiring Requirements for eFlow102NXV Models:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit 
wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited 
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. 
One such example of this is shown below. Your specific application may require different conduit knockouts to 
be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field 
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).

Optional battery enclosure must be mounted adjacent to the power supply.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 8a).

Fig. 8

Fig. 8a

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

*  Outputs are non power-limited:
  eFlow102NXV, eFlow102NX8V, eFlow102NX16V.
  Outputs are power-limited:
  eFlow102NX8DV, eFlow102NX16DV.

 Input

220VAC 50/60Hz

(non power-

limited)

Supervisory, Fire Alarm Interface

and Aux. output Connections

(power-limited)

DC Output*

Power 

Distribution

Optional Battery 

Enclosure

(non power-limited)

Battery

Connections

(non power-limited)

Содержание eFlow102N16DV

Страница 1: ..._____ Address ____________________________________________________ Phone ______________________ eFlow102NV eFlow102NXV 10A 12VDC eFlow102N8V eFlow102NX8V 10A 12VDC Eight 8 Fused Outputs eFlow102N16V e...

Страница 2: ...tput Range V eFlow102NV 10 03 13 2 10 03 13 2 10A 2 1A 5A 250V 15A 32V 760 N A 1 P eFlow102NXV P eFlow102N8V 10 03 13 2 10 03 13 2 10A 2 1A 5A 250V 15A 32V 760 PD8 8 2 5A P eFlow102NX8V 2 5A P eFlow10...

Страница 3: ...ut will not be affected by Low Power Disconnect or Fire Alarm Interface Connect device to terminals marked AUX Fig 1f pg 5 5 For Access Control applications batteries are optional When batteries are n...

Страница 4: ...riate reporting device Wiring Use 18 AWG or larger for all low voltage power connections Note Take care to keep power limited circuits separate from non power limited wiring 220VAC Battery Maintenance...

Страница 5: ...s present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maximum cha...

Страница 6: ...2 3 4 5 6 7 8 D1 INPUT R1 LED From Power Supply Board Factory Installed Replace fuses with the same type and rating 3 5A 250V DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs N COMMON POW...

Страница 7: ...one 1 12VDC stand by battery Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 7AH Rechargeable batteries are the largest batteries that can fit in this enclosure An e...

Страница 8: ...ptional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply Note...

Страница 9: ...tteries L G N NC C NO NC C NO BAT FAIL AC FAIL DC AC AC1 DC BAT AUX TRIGGER EOL SUPERVISED 5A 250V RESET GND NO disable enable 2 hr 1 min AC DELAY SHUTDOWN O N 220VAC power mains Battery connections D...

Страница 10: ...tional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply Note...

Страница 11: ...342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25...

Страница 12: ...mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38...

Страница 13: ...hotoelectric w 135 o Thermal 0 05 50 2112 24TSRB Photoelectric w 135 o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 245...

Страница 14: ...trol of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state ch...

Страница 15: ...sponsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A...

Страница 16: ...65AH 6A 10A 1 5A 10A Over 4 Hours 10A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Tr...

Отзывы: