eFlow104NK8(D)
- 7 -
Fig. 3 - eFlow104NK8(D)
DC Output to devices
(
eFlow104NK8
- non power-limited,
eFlow104NK8D
- power-limited)
eFlow104NB
Power Supply
– DC
+
– BAT
+
L G N
Tamper Switch
AC FAIL NC C NO NC C NO BAT FAIL
PTC
Protected
Outputs on
eFlow104NK8D
PDS8(CB)
+ INP1
--
PWR1 +
OFF
IN1
IN2
Out
1
<
1 off
2>
PWR1 +
PWR2 +
PWR2 +
COM (--- )
COM (--- )
+ INP2
--
IN2 Fuse
IN1 Fuse
Common Power Outputs (NEG)
N
P
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
1
2
3
4
5
6
7
8
10
10
3
3
3
3
3
3
3
3
Out
2
<
1 off
2>
Out
3
<
1 off
2>
Out
4
<
1 off
2>
Out
5
<
1 off
2>
Out
6
<
1 off
2>
Out
7
<
1 off
2>
Out
8
<
1 off
2>
Power Output
Factory wired to
PDS8(CB) and VR6
(non power-limited)
Battery Output
(non power-limited)
Supervisory connections (power-limited)
Spade Lugs to connect
to the compatible board
24VDC from
eFlow104NB
12VDC from VR6
(factory connected)
Optional Rechargeable Stand-by Battery
for UL294 Applications
Note: 12V batteries required for
ULC-S319 installations.
Optional Rechargeable Stand-by Battery
for UL294 Applications
Note: 12V batteries required for
ULC-S319 installations.
CAUTION: Use two (2) 12VDC stand-by batteries.
Keep power-limited wiring separate from non power-limited.
Use minimum 0.25” spacing.
12AH Rechargeable batteries are the largest batteries that
can fit in this enclosure.
A UL listed external battery enclosure must be used if using
40AH or 65AH batteries.
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Fig. 3a