- 4 -
ALTV1224DC220 Series
Door
CAUTION: De-energize unit prior to servicing. For continued protection against
fire hazard replace fuse with the same type and rating. Do not expose unit to rain or moisture.
Wire Strap
(from
Enclosure
to Door)
220VAC
power
mains
Divider
Switch disables power mains
line voltage input.
If stand-by battery (batteries) are
connected the DC output remains on.
OFF ON
3.5A 250V
For continuous protection against risk of fire
replace fuses with same type and rating.
common
outputs
protected
outputs
P
N
N
P
S
XFMR Input
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
N
P
Used on PTC Models
(example: ALTV1224DC1CB220)
P
N
N
P
S
XFMR Input
common
outputs
protected
outputs
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
N
P
SW1
24VDC output - OFF
12VDC output - ON
OFF - 24V
ON - 12V
ON
OFF - 24V
ON - 12V
ON
Trimpot
Adjusts output voltage
on power supply
Ground
Lug
ALTV1224DC1/CB Terminal Identification:
OLS127220 - Power Supply
Terminal Legend
Function/Description
L, N
220VAC power mains connection.
– DC +
12VDC or 24VDC @ 4A total continuous output.
– BAT +
Stand-by battery connections. Maximum charge rate 0.5A.
PD16W/PD16WCB - Power Distribution Module
Terminal Legend
Function/Description
1P - 16P
Positive DC power outputs.
1N - 16N
Negative DC power outputs.
Fig. 2