background image

AL842ADA220

NAC Power Extender

Installation Guide

(see Application Guide for additional information)

Rev. 072108

More than just power.

TM

Installing Company:  _______________ Service Rep. Name:  __________________________________  

Address:  _____________________________________________  Phone #:  __________________

Содержание AL642ADA220

Страница 1: ... see Application Guide for additional information Rev 072108 More than just power TM Installing Company _______________ Service Rep Name __________________________________ Address _____________________________________________ Phone __________________ ...

Страница 2: ...king range 198VAC 256VAC 50 60 Hz 2 5A Two 2 Class A Style Z or two 2 Class B Style W X Y FACP inputs Two 2 NC dry contact trigger inputs Output 24VDC voltage regulated power limited outputs 8A max total alarm current 2 5A max current per output Two auxiliary outputs rated at 1A each 1A continuous 1A AC disconnect Programmable supervised indicating circuit outputs Four 4 Class B Style W X Y or Fou...

Страница 3: ...n Guide for AL642ADA220 AL842ADA220 AL1042ADA220 Power Supply Specifications pg 3 Stand by Specifications pg 3 Output Programming Selection Table pg 4 Sync Mode Selection Table pg 4 Terminal Identification Table pgs 5 6 LED Status Indication Table pg 6 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two uppe...

Страница 4: ... a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe allowing audible notification appliances horns and visual notification appliances strobes to be silenced deactivated at the same time Gentex Sync Mode Gentex is a registered trademark of Gentex Corporation 1 2 3 4 This mode is designed to work with the Gentex series of horns strobes and horn strobes to ...

Страница 5: ...OUT3 OUT4 Supervised Notification appliances are connected to these regulated outputs see Application Guide pg 2 4 Each power limited output will supply 2 5A Total supply current is 8A see note below Outputs are controlled by designated Input 1 IN1 or Input 2 IN2 Output Programming Selection Table pg 4 Maximum line loss or voltage drop tested with 2 5V Loop 1 Loop 2 Loop 3 Loop 4 Used for Class A ...

Страница 6: ...onds Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED Diagnostics AL800ADA Power Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is supplying power OFF ON No D...

Страница 7: ... Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 8A 8000mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minutes 0 0833 hours H I...

Страница 8: ... and IN2 Non Supervised Class E Factory Installed Board Interface Cable AC Magnetic Door Holder line ground neutral Unswitched 120VAC power mains supervised non power limited Supervised power limited Non supervised power limited Class E Non Supervised Class E Non Supervised Class E Compatible Special Application Devices See Compatibility List non power limited Stand by battery connection non power...

Страница 9: ...nect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 2b Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output...

Страница 10: ...or 2112 24T D Photoelectric w 135 o Thermal 0 05 50 System Sensor 2112 24TSRB Photoelectric w 135 o Thermal Supervisory Relay 15 45 System Sensor 2312 24TB Photoelectric 0 12 50 System Sensor 2412 12 volt Photoelectric 0 12 77 System Sensor 2412AT 12 volt Photoelectric 0 12 58 System Sensor 2412TH 12 volt Photoelectric 0 12 77 System Sensor 2424 Photoelectric 0 10 41 System Sensor 2424TH Photoelec...

Страница 11: ...s compatible with AL642ADA220 AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30 R 14E 23 R 10T 23 R 20E 40 R 14T 23 R 24E 40 ...

Страница 12: ...IAL842ADA220 H10U MEMBER 6 0 152 4mm 1 5 38 1mm 2 5 63 5mm 1 0 25 4mm 2 75 69 9mm 2 75 69 9mm 4 5 114 3mm 4 5 114 3mm 14 5 368 3mm 1 0 25 4mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 1 25 31 75mm 1 25 31 75mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm Enclosure Dimensions 1...