Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level
(refer to Power Supply Output Selections chart).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the bat-
tery terminal and at the board terminals marked [+ BAT --- ] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharge is 0.7A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
Red (DC)
Green (AC)
Red (BAT)
Power Supply Status
ON
ON
ON
Normal operating condition.
ON
OFF
ON
Loss of AC. Stand-by battery supplying power.
OFF
ON
OFF
No DC output, Battery Trouble
OFF
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
ON
ON
OFF
Battery missing / Low
Terminal Identification:
L, G, N
Connect 220VAC (working range 198VAC - 256VAC), 50/60Hz to these terminals:
L to hot, N to neutral, G to ground.
– DC +
12VDC / 24VDC @ 6A continuous non power-limited output.
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized
when AC power is present. Contact rating 1A @ 28VDC. AC or brownout fail is reported within 1 min-
ute of event. To delay reporting for up to 6 hrs., cut “AC delay” jumper and reset power to unit.
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power
is present. Contact rating 1A @ 28VDC. A removed battery is reported within 5 minutes. Battery recon-
nection is reported within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.
+ BAT ---
Stand-by battery connections. Maximum charge current 0.7A.
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected]. Lifetime Warranty, Made in U.S.A.
IIAL600XB220 - Rev. 120300
E16P
Fig. 2
+ DC
---
BAT FAIL NC C NO NC C NO
+ BAT
---
AC FAIL
DC
AC
BAT
L
G
N
5A 250V
OFF - 24V ON - 12V
ON
Fig. 2a
+ DC
---
BAT FAIL NC C NO NC C NO
+ BAT
---
AC FAIL
DC
AC
BAT
L
G
N
5A 250V
OFF - 24V ON - 12V
ON
MEMBER