Specifications:
Power Supply Output Specifications:
Output
Switch Position
12VDC
SW1 - ON (Fig. 1b, pg. 4)
24VDC
SW1 - OFF (Fig. 1b, pg. 4)
Stand-by Specifications
(total current shown)
:
Output
4 hr. of Stand-by and
5 Minutes of Alarm
24 hr. of Stand-by and
5 Minutes of Alarm
60 hr. of Stand-by and
5 Minutes of Alarm
12VDC / 40AH Battery
Stand-by = 6.0A
Alarm = 6.0A
Stand-by = 1.0A
Alarm = 6.0A
Stand-by = 300mA
Alarm = 6.0A
24VDC / 12AH Battery
–
Stand-by = 200mA
Alarm = 6.0A
–
24VDC / 40AH Battery
Stand-by = 6.0A
Alarm = 6.0A
Stand-by = 1.0A
Alarm = 6.0A
Stand-by = 300mA
Alarm = 6.0A
ON
OFF - 24V
ON - 12V
Input:
• Input 115VAC / 60Hz, 3.5A.
Output:
• 12VDC or 24VDC selectable output(s).
• 6A continuous supply current at 12VDC or 24VDC.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7A.
• Zero voltage drop when switched over to
battery backup.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
• Battery presence supervision (form “C” contacts).
LED Indicators:
• AC input, DC output and Battery LED indicators.
Additional Features:
• Power supply, enclosure, cam lock and
battery leads.
• All models are available in red enclosure
(add an “R” suffix to the part # e.g.
AL600ULPD8R).
Output
Voltage
Voltage
Type
Output Current
Frequency
Ripple
Voltage
Normal
Stand-by
Stand-by
Battery
Minimum
Operating
Time
Maximum
(alarm)
Stand-by
Battery
Minimum
Operating
Time
DC Output
12VDC and 24VDC
DC
See Stand-by Specifications, pg. 3
N/A
300mV