Maintenance: 

Unit should be tested at least once a year for the proper operation as follows: 

Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level

(refer to Power Supply Voltage Output Specifications chart). 

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the bat­

tery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery connection wires. 

Note: Maximum charging current under discharge is 0.7A. 

Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed. 

LED Diagnostics: 

Red (DC) 

Green (AC) 

Power Supply Status 

ON 

ON 

Normal operating condition. 

ON 

OFF 

Loss of AC. Stand-by battery supplying power. 

OFF 

ON 

No DC output. 

OFF 

OFF 

Loss of AC. Discharged or no stand-by battery. No DC output. 

Red (Bat) 

Battery Status 

ON 

Normal operating condition. 

OFF 

Battery fail/low battery. 

Terminal Identification: 

Terminal Legend  Function/Description 

L, G, N 

Connect 220VAC (working range 198VAC - 256VAC), 50/60 Hz to these terminals: 

L to hot, N to Neutral, G to ground. 

+ DC --­

12VDC @ 4A or 24VDC @ 3A continuous output. 

AC Fail 

NC, C, NO 

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized 

when AC power is present. Contact rating 1A @ 28VDC. AC or brownout fail is reported within 1 

minute of event. To delay reporting of up to 6 hrs., cut “AC delay” jumper and reset power to unit. 

Bat Fail 

NC, C, NO 

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized 

when DC power is present. Contact rating 1A @ 28VDC. 

+ BAT --­

Stand-by battery connections. Maximum charge current 0.7A. 

Fig. 2 

Fig. 2a 

+

 DC 

---

NC  C  NO  NC  C  NO 

 BA

T  

---

AC  DC  Bat 

Risk of Fire, 
Replace Fuses 
As Marked 

AC Fail

Bat Fail 

J1 

SW1 

5A  250V 

15A  250V 

AC Delay 

15 

OFF - 24V 

ON - 12V 

ON

 

J1 

AC Delay 

Altronix is not responsible for any typographical errors. 

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 
website: www.altronix.com, e-mail: [email protected]. Lifetime Warranty, Made in U.S.A. 
IIAL400XB2V - Rev. 112112 