 AL300ULXJ Installation Guide 

- 3 -

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 

local codes and authorities having jurisdiction. Product is intended for indoor use only. 

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 

  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 8)

. Secure enclosure to earth ground. 

2. Set the unit to the desired DC output voltage by setting SW1

 (Fig. 1c, pg. 5)

 to the appropriate position 

 

(Power Supply Output Specification Chart, pg. 2).

3. Secure cabinet to earth gourd. Connect AC power (115VAC, 60 Hz) to the terminals marked [L, N] 

 

(Fig. 1, pg. 5)

. Green “AC” LED on power supply board will turn on. This light can be seen through the 

  LED lens on the door of the enclosure. Use 14 AWG or larger for all power connections (Battery, DC output, 

  AC input). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

 

Keep power-limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, 

  Battery Wires). Minimum 0.25” spacing must be provided.

  For Fire Alarm applications the outputs are “Special Applications” only, see list 

(refer to Appendix A, pg. 6)

4. Measure output voltage before connecting devices. This helps avoiding potential damage. 

  When servicing the unit, AC mains should be removed.

5. Connect devices to the terminals marked [+ DC –] 

(Fig. 1, pg. 5)

.

6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

  in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

  Connect one (1) 12VDC battery to the terminals marked [+ BAT –] for 12VDC operation. 

  Use two (2) 12VDC batteries wired in series for 24VDC operation.

7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL 

(Fig. 1a, pg. 5)

 supervisory 

  relay outputs.

 

Note:

 When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be

  utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper 

 

(Fig. 1b, pg. 5)

8. Please ensure that the cover is secured with the provided key lock.

Wiring:

Use 14 AWG or larger for all power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 

Under normal load conditions, the DC output voltage should be checked for proper 

   

voltage level (

refer to Power Supply Voltage Output Specifications chart

).

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified 

   

voltage both at the battery terminal and at the board terminals marked [+ BAT –] to 

   

ensure that there is no break in the battery connection wires.

Note:

 

Maximum charging current under discharge is 0.7A.

Note:

 

Expected battery life is 5 years, however it is recommended changing batteries 

   

in 4 years or less if needed.

Содержание AL300ULXJG

Страница 1: ...add a G suffix to the part number AL300ULXJ Power Supply Charger Installation Guide Rev 030619 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Страница 2: ...t s Short circuit and thermal overload protection LED Indicators AC input DC output and Battery LED indicators Battery Backup Built in charger for sealed lead acid or gel type batteries Automatic switch over to stand by battery when AC fails Maximum charge current 0 7A Zero voltage drop when switched over to battery backup Supervision AC fail supervision form C contacts Low battery and battery pre...

Страница 3: ...to Appendix A pg 6 4 Measure output voltage before connecting devices This helps avoiding potential damage When servicing the unit AC mains should be removed 5 Connect devices to the terminals marked DC Fig 1 pg 5 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired ...

Страница 4: ...Relay normally ener gized when AC power is present Contact rating 1A 28VDC AC Fail condition will report approximately within one 1 minute after loss of AC To delay report for 6 hours cut jumper J1 on the Power Supply Board AC trouble output delay option If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds Bat Fail NC C NO Indicates low battery c...

Страница 5: ...against risk of electric shock and fire hazard replace fuse with the same type and rating Do not expose to rain or moisture CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 115VAC power mains non power limited Optional Rechargeable Stand by Battery Optional Recharge...

Страница 6: ...ric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 0 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 0 05 23 4WTA B 12 24 volt I3 Photo w Therm Sounder 0 05 35 4WTR B 12 ...

Страница 7: ...AL300ULXJ Installation Guide 7 Notes ...

Страница 8: ...5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm Enclosure Dimensions H x W x D approximate 18 x 14 5 x 4 625 457 2mm x 368 3mm x 117 5mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info al...

Отзывы: