background image

Altronix Corp.

140 58th St. Brooklyn, NY

7315-1335:0100

Power Units

For a grey enclosure add a “G” suffix to the part number

AL300ULXJ

Power Supply/Charger

Installation Guide

Rev. 030619

More than just power.

TM

Installing Company:  _______________ Service Rep. Name:  __________________________________  

Address:  _____________________________________________  Phone #:  __________________

Содержание AL300ULXJG

Страница 1: ...add a G suffix to the part number AL300ULXJ Power Supply Charger Installation Guide Rev 030619 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Страница 2: ...t s Short circuit and thermal overload protection LED Indicators AC input DC output and Battery LED indicators Battery Backup Built in charger for sealed lead acid or gel type batteries Automatic switch over to stand by battery when AC fails Maximum charge current 0 7A Zero voltage drop when switched over to battery backup Supervision AC fail supervision form C contacts Low battery and battery pre...

Страница 3: ...to Appendix A pg 6 4 Measure output voltage before connecting devices This helps avoiding potential damage When servicing the unit AC mains should be removed 5 Connect devices to the terminals marked DC Fig 1 pg 5 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired ...

Страница 4: ...Relay normally ener gized when AC power is present Contact rating 1A 28VDC AC Fail condition will report approximately within one 1 minute after loss of AC To delay report for 6 hours cut jumper J1 on the Power Supply Board AC trouble output delay option If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds Bat Fail NC C NO Indicates low battery c...

Страница 5: ...against risk of electric shock and fire hazard replace fuse with the same type and rating Do not expose to rain or moisture CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 115VAC power mains non power limited Optional Rechargeable Stand by Battery Optional Recharge...

Страница 6: ...ric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 0 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 0 05 23 4WTA B 12 24 volt I3 Photo w Therm Sounder 0 05 35 4WTR B 12 ...

Страница 7: ...AL300ULXJ Installation Guide 7 Notes ...

Страница 8: ...5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm Enclosure Dimensions H x W x D approximate 18 x 14 5 x 4 625 457 2mm x 368 3mm x 117 5mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info al...