AL175ULX

Overview:

Altronix AL175ULX is a power-limited power supply/charger that will convert 115VAC / 60Hz input into two 
individually PTC protected auto-resettable 12VDC or 24VDC outputs (see specifications). It is intended for use 
in applications requiring UL Listing for Access Control System Units (UL 294) and applications requiring an 
interface with the Fire Alarm Control Panels.

Specifications:

Agency Listings:

•  UL Listed for Access Control Systems (UL294).
  CUL Listed - CSA Standard C22.2
  No.205-M1983, Signal Equipment.
•  CSFM - California State Fire Marshal Approved.
•  MEA - NYC Dept. of Buildings Approved.
•  NFPA 101 (Life Safety).

Input:

•   Input 115VAC, 60Hz, 0.6A.

Output:

•  12VDC or 24VDC selectable output.
•  Class 2 Rated power-limited outputs.
•  1.75A continuous supply current @ 
  12VDC or 24VDC.
•  Aux relay output (form “C” contacts).
•  Filtered and electronically regulated output.
•  Short circuit and thermal overload protection.

Battery Backup:

•  Maximum charge current: 400mA.
•  Automatic switch over to stand-by battery 
  when AC fails.

Supervision:

•  AC fail supervision (form “C” contacts). 
•  Dry trigger output (form “C” contacts). 

Fire Alarm Interface:

•  Dry trigger input.

Visual Indicators:

•  AC input and DC output LED indicators.

Added Features:

•  Includes power supply, transformer, and enclosure.

Enclosure Dimensions:

  13.5” x 13” x 3.25” 
  (342.9mm x 330.2mm x 82.6mm)

Power Supply Output Specifications:

Output 
VDC

Switch Position

Max. Stand-by 

Load DC

Max. Alarm 

Load DC

Battery 

(optional)

12VDC

SW1 OFF

1.75A

1.75A

12VDC

24VDC

SW1 ON

1.75A

1.75A

24VDC

Stand-by Specifications:

Output

4 hr. of Stand-by and 5 Minutes of Alarm

12VDC / 7 AH Battery

Stand-by = 1.25A
Alarm = 1.25A

24VDC / 7 AH Battery

Installation Instructions:

The AL175ULX should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 
as well as all applicable Local Codes.
See Terminal Identification Chart on page 3 for a description of each terminal function.
1.  Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 
  enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two 
  holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper 
  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 
  (Enclosure Dimensions, pg. 8).
2. Connect AC power to the black and white flying leads of the transformer. Secure green wire lead to earth 
  ground. Use 18 AWG or larger for all power connections (Battery, AC input, DC outputs). Use 22 AWG to 
  18 AWG for power-limited circuits (trigger inputs, dry outputs).
  Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery 
  Wires). Minimum 0.25” spacing must be provided.
  CAUTION: Do not touch exposed metal parts. 
  Shut branch circuit power before installing or servicing equipment. 
  There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Set the AL175ULX to the desired DC output voltage by setting switch SW1 to the appropriate position 
  (Power Supply Output Specification Table).
4. Measure output voltage before connecting devices. This helps avoiding potential damage.

Содержание AL175ULX

Страница 1: ...Rev 121307 More than just power TM AL175ULX Access Control Power Supply Charger Altronix Corp 140 58th St Brooklyn NY...

Страница 2: ...s of Alarm 12VDC 7 AH Battery Stand by 1 25A Alarm 1 25A 24VDC 7 AH Battery Installation Instructions The AL175ULX should be installed in accordance with article 760 of The National Electrical Code or...

Страница 3: ...wires Note Maximum charging current under discharges is 400mA Note Expected battery life is 5 years however it is recommended changing batteries in 4 years or less if needed LED Diagnostics Red DC Gre...

Страница 4: ...ead Input 115VAC 60Hz 0 6A Green Ground Wire Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery CAUTION De energize unit prior to servicing For continued protection against...

Страница 5: ...STRIKE TRG2 TRG1 AUX AUX COM Fig 2 Typical single mag lock or door strike installation with fire alarm tie in using trigger controlled output FACP MAG LOCK MAG LOCK ACCESS CONTROL DEVICE LOCK STRIKE T...

Страница 6: ...n using aux output installation FACP MAG LOCK ACCESS CONTROL DEVICE AUX FACP AUX NO RESET SWITCH FACP MAG LOCK ACCESS CONTROL DEVICE LOCK STRIKE TRG2 TRG1 C NO NC COM Fig 5 Latching fire alarm tie in...

Страница 7: ...AL175ULX 7 Notes...

Страница 8: ...in U S A IIAL175ULX C21R MEMBER Enclosure Dimensions H x W x D approximate 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 13...

Отзывы: