AL1042ULADA / R1042ULADA Installation Guide
- 9 -
NEC Power-Limited Wiring Requirements for AL1042ULADA Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
One such example of this is shown below. Your specific application may require different conduit knockouts to
be used. Any conduit knockouts may be used. For power- limited applications, use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Optional battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.
Note:
Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire
(Fig. 6a).