- 4 -

AL1042UL2ADA

Output Programming Selection Table:

Outputs must be programmed independently (OUT1 - OUT4)

Function

Switch Positions

Descriptions

ON

OFF

Input to Output

1

2, 3

Output follows signal it receives from the corresponding input

Follower Mode

(i.e. FACP Sync module - maintains synchronization of  
notification appliance circuit.

Temporal Code 3

3

1, 2

Enables Temporal Code 3 signal generation output. 

Mode

This mode will accept a steady or a pulsing input.

Steady Mode

1, 2, 3

A steady output signal will be generated. This mode 
will accept steady or pulsing input.

For the above modes Dip Switch 4 determines which Input controls 
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.

Sync Mode Selection Table:

Function

Switch Positions

Descriptions

ON

OFF

Amseco

1, 3, 4

2

This mode is designed to work with the Amseco 

Sync Mode*

series of horns, strobes, and horn/strobes to provide a means of syn-
chronizing the Temporal-coded horns, synchronizing the flash timing
of the strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.

Faraday

2, 4

1, 3

This mode is designed to work with the Faraday 

Sync Mode*

series of horns, strobes, and horn/strobes to provide a means of syn-
chronizing the Temporal-coded horns, synchronizing the flash timing
of the strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.

Gentex

1, 2,

This mode is designed to work with the Gentex

®

Commander GOS  

Sync Mode*

3, 4

and ST/HS series of horns, strobes, and horn/strobes to provide a 
means of synchronizing the Temporal-coded horns, synchronizing the 

Gentex is a registered

flash timing of the strobe, and silencing the horns of the horn/strobe 

trademark of Gentex Corporation.  

combination over a two-wire circuit while leaving strobes active.

System Sensor

1, 2, 4

3

This mode is designed to work with the SpectrAlert

TM

series of

Sync Mode*

horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the one-second flash timing

System Sensor is a registered

of the strobe, and silencing the horns of the horn/strobe combination

trademark of Honeywell.

over a two-wire circuit while leaving strobes active.

Wheelock

2, 3, 4

1

This mode is designed to work with the Wheelock series of

Sync Mode*

horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the one-second flash timing
of the strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.

Note:

The AL1042UL2ADA will only synchronize horns, horn strobes and strobes that contain synchronization capability.

Contact signal manufacturer for more detailed info. The same synchronization mode must be selected for all outputs.

*It is required to control visual notification appliances (strobes) via input 1 [IN1] and audible notification 
appliances (horns) via input 2 [IN2]. This allows audible notification appliances (horns)  to be silenced while 
visual notification appliances (strobes) continue to operate.

(AL842LGK Board)

Output Dip Switches

INPUT SELECT

TEMPORAL

STROBE SYNC

IN>OUT SYNC

1
 

 

2
 

 

3
 

 

4

Содержание AL1042UL2ADA

Страница 1: ...Rev 080306 AL1042UL2ADA NAC Power Extender Installation Guide See Application Guide for additional information...

Страница 2: ...emory helps identify intermittent loop problems Common trouble input and output Ground fault detection Added Features Unit includes power supply logic board enclosure cam lock and battery leads Enclos...

Страница 3: ...uding Place the enclosure s upper keyholes over the two upper screws level and secure Mark the position of the lower two holes Remove the enclosure Drill the lower holes and install the three fastener...

Страница 4: ...1 2 This mode is designed to work with the Gentex Commander GOS Sync Mode 3 4 and ST HS series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchroniz...

Страница 5: ...ach power limited output will supply 2 amp Two 2 outputs may be connected in parallel for a OUT3 maximum NAC output capability of 4 amp Total supply current is 6 5 amp see note below Outputs OUT4 are...

Страница 6: ...tput setting or approximately 10 5VDC 12VDC output setting Battery presence detection will report within 3 minutes after battery remains undetected missing or removed A restored battery will report wi...

Страница 7: ...ing washer between the board and standoff of the lower right power supply board mounting screw Fig 2B Fig 2 Optional Hookup Diagram Fig 2A Fig 2D Ground Fault Detection Enabled Ground Fault Detection...

Страница 8: ...ower Supply Output Specifications Chart Battery Test Under normal load conditions check that the battery is fully charged Check specified voltage both at battery terminal and at the board terminals ma...

Страница 9: ...ent ratings Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10 amp 10000mA 0mA mA D Total alarm current mA mA E Total current ratings...

Страница 10: ...AL1042UL2ADA 1 50 1 25 2 50 6 00 2 50 1 50 2 50 1 50 1 00 1 50 1 00 1 50 2 75 4 50 4 50 1 00 1 00 1 25 1 50 8 50 1 00 1 00 2 75 18 00 14 50 18 00 18 00 14 50 Enclosure Dimensions 18 H x 14 5 W x 4 62...

Страница 11: ...AL1042UL2ADA 11 Notes...

Страница 12: ...Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIAL1042UL2ADA J26G MEMBER Notes Altronix is not responsib...

Отзывы: