Altronix AL1042UL2ADA Скачать руководство пользователя страница 1

Rev. 080306

AL1042UL2ADA

NAC Power Extender

Installation Guide

(See Application Guide for additional information)

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание AL1042UL2ADA

Страница 1: ...Rev 080306 AL1042UL2ADA NAC Power Extender Installation Guide See Application Guide for additional information...

Страница 2: ...emory helps identify intermittent loop problems Common trouble input and output Ground fault detection Added Features Unit includes power supply logic board enclosure cam lock and battery leads Enclos...

Страница 3: ...uding Place the enclosure s upper keyholes over the two upper screws level and secure Mark the position of the lower two holes Remove the enclosure Drill the lower holes and install the three fastener...

Страница 4: ...1 2 This mode is designed to work with the Gentex Commander GOS Sync Mode 3 4 and ST HS series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchroniz...

Страница 5: ...ach power limited output will supply 2 amp Two 2 outputs may be connected in parallel for a OUT3 maximum NAC output capability of 4 amp Total supply current is 6 5 amp see note below Outputs OUT4 are...

Страница 6: ...tput setting or approximately 10 5VDC 12VDC output setting Battery presence detection will report within 3 minutes after battery remains undetected missing or removed A restored battery will report wi...

Страница 7: ...ing washer between the board and standoff of the lower right power supply board mounting screw Fig 2B Fig 2 Optional Hookup Diagram Fig 2A Fig 2D Ground Fault Detection Enabled Ground Fault Detection...

Страница 8: ...ower Supply Output Specifications Chart Battery Test Under normal load conditions check that the battery is fully charged Check specified voltage both at battery terminal and at the board terminals ma...

Страница 9: ...ent ratings Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10 amp 10000mA 0mA mA D Total alarm current mA mA E Total current ratings...

Страница 10: ...AL1042UL2ADA 1 50 1 25 2 50 6 00 2 50 1 50 2 50 1 50 1 00 1 50 1 00 1 50 2 75 4 50 4 50 1 00 1 00 1 25 1 50 8 50 1 00 1 00 2 75 18 00 14 50 18 00 18 00 14 50 Enclosure Dimensions 18 H x 14 5 W x 4 62...

Страница 11: ...AL1042UL2ADA 11 Notes...

Страница 12: ...Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIAL1042UL2ADA J26G MEMBER Notes Altronix is not responsib...