42ADA220 Application Guide
- 5 -
6. Using Single FACP Output.
When only one FACP output is available, you may connect both Input 1 and Input 2 to it.
Wire [RET1 +] and [RET1 –] to [INP2 +] and [INP2 –].
Both Visual and Audible appliances will be activated simultaneously
(Fig 6a)
.
EOL or Next Device
For Class A configuration
return to FACP
FACP
+ RET2 –
+ IN2 –
+ RET1 –
+ IN1 –
C "DRY1" NC
C "DRY2" NC
Control Circuit
No Notification
Appliances Allowed
Fig. 6a
Содержание AL1042ADA220