AL1024NK1 Installation Guide

LED Diagnostics:

AL1024ULXB2 - Power Supply/Charger

Red (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

AL1024ULXB2 - Power Supply Board

Terminal Legend

Function/Description

L, N

Connect 115VAC to these terminals: L to hot, N to neutral 

(Fig. 1a, pg. 4)

.

+ DC –

Factory connected to VR6 

(Fig. 1d, pg. 4)

.

AC Fail

NC, C, NO

Used to notify loss of AC power, e.g.connect to audible device or alarm panel. 

Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. 

AC or brownout fail is reported within 1 minute of event. 

To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit 

(Fig. 1f, pg. 4)

.

Bat Fail

NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. 

Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. 

A removed battery is reported within 1 minute. 

Battery reconnection is reported within 1 minute.

Low battery threshold: approximately 21VDC 

(Fig. 1b, pg. 4)

.

– BAT +

Stand-by battery connections. Maximum charge current 3.6A 

(Fig. 1c, pg. 4)

.

VR6 - Voltage Regulator

Terminal Legend

Function/Description

+ IN –

Power input from AL1024ULXB2, factory installed.

+ OUT –

5VDC @ 6A or 12VDC @ 6A, depending on SW1 setting.

Fig. 1 - 

AL1024ULXB2 Board Configuration

1a

1b

1d

1c

1e

1f

L

G

N

BAT FAIL

AC FAIL

NC

C

NO

NC

C

NO

AC

DC

-   BAT   

+

+   DC   - 

AC DELAY

Содержание AL1024NK1

Страница 1: ...4ULXB2 Power Supply Charger 1 VR6 Voltage Regulator Installation Guide Rev 1024NK1_022322 More than just power TM Installing Company ________________ Service Rep Name _________________________________...

Страница 2: ...00mA Alarm 10A For Access Control applications battery capacity for 10A supply current 1 hr for 24VDC 12AH battery 6 5 hrs for 24VDC 65AH battery See battery size calculation worksheet for other batte...

Страница 3: ...terminals marked OUT on VR6 Fig 2b pg 5 Carefully observe correct polarity 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of...

Страница 4: ...esent Contact rating 1A 28VDC AC or brownout fail is reported within 1 minute of event To delay reporting for up to 6 hrs cut AC Delay jumper and reset power to unit Fig 1f pg 4 Bat Fail NC C NO Used...

Страница 5: ...y board is factory set for 24VDC Use two 2 12VDC stand by batteries Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 7AH Rechargeable batteries are the largest batter...

Страница 6: ...________________ A G Alarm duration Hours 15 Min 0 25 Hour Alarm ________________ H H Battery capacity required for Alarm E F G ________________ AH I Total calculated battery capacity D H ___________...

Страница 7: ...it is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the...

Страница 8: ...20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm...

Отзывы: