- 4 -
Mseries
11.Connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] and [Power Fail]
supervisory relay outputs marked [NO, C, NC] on power supply board (Fig. 1A, pg. 5; Fig. 2A, pg. 6; Fig. 3A, pg. 7;
Fig. 4A, pg. 8). Use 22 AWG to 18 AWG for AC Fail & Low Battery reporting.
Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used to provide
a visual indication of AC power on.
12. Please insure that the cover is secured with the provided Key Lock.
Output Voltage and Stand-by Specification Charts:
AL300ULM
Output
Switch
4 hr. of Stand-by &
24 hr. of Stand-by &
60 hr. of Stand-by &
Position
5 Minutes of Alarm
5 Minutes of Alarm
5 Minutes of Alarm
12VDC / 40 AH Battery
Closed
Stand-by = 2.5 amp
Stand-by = 1.0 amp
Stand-by = 300mA
Alarm = 2.5 amp
Alarm = 2.5 amp
Alarm = 2.5 amp
24VDC / 12 AH Battery
Open
Stand-by = 200mA
Alarm = 2.5 amp
24VDC / 40 AH Battery
Open
Stand-by = 2.5 amp
Stand-by = 1.0 amp
Stand-by = 300mA
Alarm = 2.5 amp
Alarm = 2.5 amp
Alarm = 2.5 amp
AL400ULM
Output
Switch
4 hr. of Stand-by &
24 hr. of Stand-by &
60 hr. of Stand-by &
Position
5 Minutes of Alarm
5 Minutes of Alarm
5 Minutes of Alarm
12VDC / 40 AH Battery
Closed
Stand-by = 4.0 amp
Stand-by = 1.0 amp
Stand-by = 300mA
Alarm = 4.0 amp
Alarm = 4.0 amp
Alarm = 4.0 amp
24VDC / 12 AH Battery
Open
Stand-by = 200mA
Alarm = 3.0 amp
24VDC / 40 AH Battery
Open
Stand-by = 3.0 amp
Stand-by = 1.0 amp
Stand-by = 300mA
Alarm = 3.0 amp
Alarm = 3.0 amp
Alarm = 3.0 amp
AL600ULM
Output
Switch
4 hr. of Stand-by &
24 hr. of Stand-by &
60 hr. of Stand-by &
Position
5 Minutes of Alarm
5 Minutes of Alarm
5 Minutes of Alarm
12VDC / 40 AH Battery
Closed
Stand-by = 6.0 amp
Stand-by = 1.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
Alarm = 6.0 amp
Alarm = 6.0 amp
24VDC / 12 AH Battery
Open
Stand-by = 200mA
Alarm = 6.0 amp
24VDC / 40 AH Battery
Open
Stand-by = 6.0 amp
Stand-by = 1.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
Alarm = 6.0 amp
Alarm = 6.0 amp
AL1012ULM
Output
15 Minutes of Stand-by @ 10 amp
12VDC / 12 AH Battery
AL1024ULM
Output
15 mins. Stand-by /
4 hr. Stand-by /
24 hr. Stand-by /
60 hr. Stand-by /
5 mins. Alarm
5 mins. Alarm
5 mins. Alarm
5 mins. Alarm
24VDC / 12 AH Battery
7.7 amp / 9.7 amp
1.2 amp / 9.7 amp
-------------------------
-------------------------
24VDC / 65 AH Battery
-------------------------
7.7 amp / 9.7 amp
1.2 amp / 9.7 amp
200mA / 9.7 amp