![Altronix AL1002ULADAJ Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/altronix/al1002uladaj/al1002uladaj_installation-manual_2913428003.webp)
AL1002ULADAJ
- 3 -
Power Supply Specifications:
AC Input:
120VAC, 60Hz, 5A, supplied by a maximum 15A dedicated branch circuit.
Output:
Four (4) regulated supervised NAC output circuits, 24VDC, 2.5A maximum
current. One (1) aux. special application 24VDC power output circuit 1A, non-
supervised total output current must not exceed current 10A in Alarm Condition.
Battery
Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH
batteries connected in series.
Stand-by/Alarm
Current Consumption:
130mA/300mA
EOL Resistor (end of line): 2.2K (2200 Ohm), Altronix Model # AL-EOL22 (included).
Ground fault maximum
test impedance:
1000 Ohm.
Stand-by Specifications:
Stand-by Batteries
Stand-by Time Total
(A/Minutes)
Alarm Output Current
Aux. Output
24VDC/7AH
24 Hours
10A/5 minutes
–
24VDC/12AH
(use two (2) 12VDC batteries in series)
24 Hours
10A/5 minutes
50mA
24VDC/36AH
24 Hours
10A/5 minutes
1A
Note: Unit is equipped with 1A max. auxiliary output: “AUX” will remain battery backed up during
power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for
ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may,
not exceed 10A total alarm current (example: AUX = 1A, outputs up to 9A).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with
all local codes and authorities having jurisdiction.
Product is intended for indoor dry use only.
Carefully review:
Application Guide for AL602ULADAJ, AL802ULADAJ, AL1002ULADAJ
Power Supply Specifications
(pg. 3)
Stand-by Specifications
(pg. 3)
Output Programming Selection Table
(pg. 4)
Sync Mode Selection Table
(pg. 4)
Terminal Identification Table
(pgs. 5-6)
LED Status Indication Table
(pg. 6)
1. Mount the unit in the desired location. Mark and predrill holes in the wall to
line up with the top two keyholes in the enclosure. Install two upper fasteners
and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two
upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the
lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper screws.
Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 16).
Secure enclosure to earth ground (Fig. 1, pg. 3). Small terminal block wire gauges range from
16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG.
2. Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (120VAC, 60Hz)
dedicated to the Fire Alarm System.
3. Measure output voltage before connecting devices.This helps avoiding potential damage.
4. Connect battery to the terminals marked [– BAT +] on the Power Supply Board (battery leads included).
Use two (2) 12VDC batteries connected in series.
Note: If batteries being used in your installation do not fit into the AL1002ULADAJ unit, it is required to
install a separate enclosure, UL Listed for appropriate application. Separate battery enclosure is required to
have 50 cubic inches of additional open space. All wiring methods shall be in accordance with the National
Electrical Code NFPA 70/NFPA 72/ANSI and with all local codes and authorities having jurisdiction.
Battery circuits are not power-limited; provide 0.25” spacing from power-limited circuits and use separate
knockout. If additional battery enclosure is required, it must be UL Listed for the application and mounted
within 5’ of the AL1002ULADAJ enclosure in the same room; minimum 12 AWG wire in appropriate conduit
is required for connection. When using conduit, make sure it is installed in a matter where it can not turn.
5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 & IN2]
and desired output signal type (Output Programming Selection Table, pg. 4).
L N
line
ground
neutral
Fig. 1
Содержание AL1002ULADAJ
Страница 15: ...AL1002ULADAJ 15 Notes...