Altronix AL1002ULADAJ Скачать руководство пользователя страница 3

 

AL1002ULADAJ 

- 3 -

Power Supply Specifications:

AC Input:

120VAC, 60Hz, 5A, supplied by a maximum 15A dedicated branch circuit.

Output:

Four (4) regulated supervised NAC output circuits, 24VDC, 2.5A maximum 
current. One (1) aux. special application 24VDC power output circuit 1A, non-
supervised total output current must not exceed current 10A in Alarm Condition.

Battery

Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH
batteries connected in series.

Stand-by/Alarm
Current Consumption:

130mA/300mA

EOL Resistor (end of line): 2.2K (2200 Ohm), Altronix Model # AL-EOL22 (included).
Ground fault maximum
test impedance:

1000 Ohm.

Stand-by Specifications:

Stand-by  Batteries  

Stand-by Time Total 

(A/Minutes)

Alarm Output Current

Aux. Output

24VDC/7AH

24 Hours

10A/5 minutes

24VDC/12AH
(use two (2) 12VDC batteries in series)

24 Hours

10A/5 minutes

50mA

24VDC/36AH

24 Hours

10A/5 minutes

1A

Note: Unit is equipped with 1A max. auxiliary output: “AUX” will remain battery backed up during 
power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for 
ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may, 
not exceed 10A total alarm current (example: AUX = 1A, outputs up to 9A).

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 
all local codes and authorities having jurisdiction.
Product is intended for indoor dry use only. 
  Carefully review:
  Application Guide for AL602ULADAJ, AL802ULADAJ, AL1002ULADAJ
  Power Supply Specifications 

(pg. 3)

  Stand-by Specifications 

(pg. 3)

  Output Programming Selection Table 

(pg. 4)

  Sync Mode Selection Table 

(pg. 4)

  Terminal Identification Table 

(pgs. 5-6)

  LED Status Indication Table 

(pg. 6)

1.  Mount the unit in the desired location. Mark and predrill holes in the wall to 
  line up with the top two keyholes in the enclosure. Install two upper fasteners 
  and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two 
  upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the 
  lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper screws. 
  Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 16)
  Secure enclosure to earth ground (Fig. 1, pg. 3). Small terminal block wire gauges range from 
  16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG.
2. Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (120VAC, 60Hz)
  dedicated to the Fire Alarm System. 
3. Measure output voltage before connecting devices.This helps avoiding potential damage.
4. Connect battery to the terminals marked [– BAT +] on the Power Supply Board (battery leads included). 
  Use two (2) 12VDC batteries connected in series. 
 

Note: If batteries being used in your installation do not fit into the AL1002ULADAJ unit, it is required to 

  install a separate enclosure, UL Listed for appropriate application. Separate battery enclosure is required to 
  have 50 cubic inches of additional open space. All wiring methods shall be in accordance with the National 
  Electrical Code NFPA 70/NFPA 72/ANSI and with all local codes and authorities having jurisdiction. 
  Battery circuits are not power-limited; provide 0.25” spacing from power-limited circuits and use separate 
  knockout. If additional battery enclosure is required, it must be UL Listed for the application and mounted 
  within 5’ of the AL1002ULADAJ enclosure in the same room; minimum 12 AWG wire in appropriate conduit 
  is required for connection. When using conduit, make sure it is installed in a matter where it can not turn. 
5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding  input [IN1 & IN2] 
  and desired output signal type (Output Programming Selection Table, pg. 4).

L       N

line 

ground

neutral

Fig. 1

Содержание AL1002ULADAJ

Страница 1: ...Rev 101413 More than just power TM Altronix Corp 140 58th St Brooklyn NY AL1002ULADAJ NAC Power Extender Installation Guide see Application Guide for additional information...

Страница 2: ...nel and should conform to all local codes Agency Listings UL Listed Control Units for Fire Protective Signaling Systems UL 864 MEA NYC Department of Buildings Approved CSFM California State Fire Marsh...

Страница 3: ...h the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secu...

Страница 4: ...h the Faraday series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn str...

Страница 5: ...ugh OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not report a trouble condition to the FACP OUT1 OUT2 OUT3 OUT4 Supervised Notification appliances are con...

Страница 6: ...will report at approximately 20VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED D...

Страница 7: ...use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to t...

Страница 8: ...pervised Input from Power Supply BAT FAIL AC FAIL DC AC NC C NO NC C NO AC LOCAL NC C NO L N 6 3A 250V Digital Communicator or Local Annunciator Dry output Contact Form C contacts Power Limited Output...

Страница 9: ...nnunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fi...

Страница 10: ...0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10A 10 000mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes l...

Страница 11: ...WGESG24 75PWLPR W UL SSPKA24 15 75PWW UL WGES24 75WRLP WWLP UL WGESR24 75PWLPR W UL SSPKA24 15 75AWR UL WGEC24 75WR WW UL WGECA24 75PWLPR W UL SSPKA24 15 75AWW UL WGEC24 75PWR PWW UL WGECB24 75PWLPR...

Страница 12: ...UL P2WH SP UL PC2WH SP UL SCWHK UL SPSW ALERT UL SWH SP UL P2WHK UL PC2WHK UL SCWK UL SPSW CLR ALERT UL SWHK UL P2WHK P UL PC2WK UL SPSCR UL SPSW P UL SWHK P UL P2WK UL PC4R UL SPSCRH UL SPSWH UL SWK...

Страница 13: ...CH90 24MCC FW UL cUL E90H 24MCCH FW UL cUL LHSW A UL cUL RSS 24MCWH FW UL cUL CH90 24MCCH FR UL cUL EET90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL...

Страница 14: ...oelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2412AT 12 volt Photoelectric 0 12 58 2412TH 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2424TH Photoelectric 0 10 41 2451 Photoelectri...

Страница 15: ...AL1002ULADAJ 15 Notes...

Страница 16: ...12R MEMBER 1 5 38 1mm 1 0 25 4mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 25 31 75mm 1 25 31 75mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 6...

Отзывы: