Installation manual

7

ERYQ005~007ACV3

Outdoor unit for air to water heat pump

(4PW33166-1B)

 3P194375-1A

Procedure

1

Strip the insulation from the wire (20 mm).

2

Connect the connection wires between the indoor and outdoor
units so that the terminal numbers match (see wiring diagram
below). Tighten the terminal screws securely. We recommend a
flathead screwdriver to tighten the screws.
See also caution 2 under 

"Notes to observe" on page 7

  for

wiring guidelines.

3

Earth terminal installation

Use the following method when installing single core wires.

Use the following method when using round crimp-style
terminals.

4

Pull the connected wire and make sure that it does not
disconnect. Then fix the wires in place in the wire clamp. See
also 

"Notes to observe" on page 7

.

Notes to observe

Observe the notes mentioned below when wiring to the power supply
terminal board.

Use the specified wire type and connect it securely (1).

Firmly secure the wire clamp so that wire terminations do not
receive external stress (2).

Shape wires so that the service cover and stop valve cover fit
securely (3).

1

Interconnection between indoor unit and outdoor unit : when 
wire length exceeds 10 m, use Ø2.5 mm wires instead of 
Ø1.5 mm wires.

2

Power supply cable 
(refer to the unit nameplate for maximum running current)

3

Earth

4

Safety breaker

5

Earth leakage circuit breaker

NOTE

This unit must be earthed.

For earthing, follow the applicable local standard
for electrical installations.

1

Single core wire

2

Screw

3

Flat washer

1

Round crimp-style terminal

2

Screw

3

Flat washer

9

10

11

1 2 3

L N

H05VV

2

1

4

5

3

50 Hz

230 V

1 2 3

9 10 11

A'

A

AA'

2

3

1

1

3

2

3

3

2

1

1

B

B

CAUTION

1.

In case the use of stranded conductor wires is
unavoidable for one reason or another, make sure to
install round crimp-style terminals on the tip.
Place the round crimp-style terminal on the wire up to
the covered part and fasten the terminal with the
appropriate tool.

2.

When connecting the connection wires to the terminal
board using a single core wire, be sure to perform
curling.

Not executing the connections properly may cause
heat and fire.
Strip the wire at terminal block:

L

N

1

2

3

1

3

2

2

1

1

Stranded conductor wire

2

Round crimp-style terminal

1

Strip wire end to this point

2

Excessive strip length may cause electrical shock 
or leakage.

Содержание ERYQ005ACV3

Страница 1: ...INSTALLATION MANUAL ERYQ005ACV3 ERYQ006ACV3 ERYQ007ACV3 Outdoor unit for air to water heat pump ...

Страница 2: ...not use an extension cord Do not put other loads on the power supply use a dedicated power circuit Failure to do so may cause abnormal heat electric shock or fire Use the specified types of wires for electrical connections between the indoor and outdoor unit Firmly clamp the interconnecting wires so that their terminals receive no external stress Incomplete connections or clamping may cause termin...

Страница 3: ...like so that the operation noise will cause no trouble There must be sufficient space for carrying the unit into and out of the site There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet The site must be free from the possibility of flammable gas leakage in a nearby place Locate the unit so that the noise and the discharged hot air will not anno...

Страница 4: ...h between outdoor unit and indoor unit 3 m Maximum allowable height difference between outdoor unit and indoor unit 15 m Additional refrigerant required for refrigerant pipe exceeding 10 m in length 20 g m Gas pipe outer diameter 15 9 mm 5 8 Liquid pipe outer diameter 6 4 mm 1 4 100 350 1200 50 50 350 100 100 350 50 1 Wrap the insulation pipe with finishing tape from bottom to top 2 Service cover ...

Страница 5: ... the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the pipe Set exactly at the position shown below 5 Check that the flaring is properly made Connecting the refrigerant piping to the outdoor unit 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare use refrigeration oil for R410A 2 Align the centres of both flares and tigh...

Страница 6: ...ow pressure valve Lo and completely close its high pressure valve Hi The high pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling meter needle does not go back 5 Remove the covers ...

Страница 7: ...service sticker on the rear side of the stop valve cover Precautions when adding R410A Be sure to charge the specified amount of refrigerant in liquid state to the liquid pipe Since this refrigerant is a mixed refrigerant adding it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon...

Страница 8: ...op valve cover fit securely 3 1 Interconnection between indoor unit and outdoor unit when wire length exceeds 10 m use Ø2 5 mm wires instead of Ø1 5 mm wires 2 Power supply cable refer to the unit nameplate for maximum running current 3 Earth 4 Safety breaker 5 Earth leakage circuit breaker NOTE This unit must be earthed For earthing follow the applicable local standard for electrical installation...

Страница 9: ...nput may be higher than stated on the nameplate of the unit This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary...

Страница 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW33166 1B 3P194375 1A ...

Отзывы: