ERYQ005~007ACV3

 

Outdoor unit for air to water heat pump

 

3P194375-1A 

 

(4PW33166-1B)

 

Installation manual

 

4

 

I

 

NSTALLATION

 

 

 

PROCEDURE

 

Mounting the outdoor unit

 

When installing the outdoor unit, please refer to 

"Installation

guidelines" on page 2

 to select an appropriate location.

 

1

 

Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.

 

2

 

Prepare 4 sets of M8 or M10 foundation bolts, nuts and washers
each (field supply).

 

3

 

Fix the unit securely by means of the foundation bolts in
accordance with the foundation drawing.
It is best to screw in the foundation bolts until their length
remains 20 mm above the foundation surface.

 

Drain work

 

If drain work is necessary, follow the guidelines below.

 

 

Install the drain plug for drainage.

 

 

If the drain port is covered by a mounting base or floor surface,
place additional foot bases of at least 30 mm in height under the
outdoor unit's feet.

 

 

In cold areas, do not use a drain hose with the outdoor unit.
Otherwise, drain water may freeze, impairing the heating
performance. In case the use of a drain hose is unavoidable for
one reason or another, it is recommended to install a heater
tape in order to protect drain from freezing.

 

Flaring the pipe end

 

To flare each pipe end, follow the procedure below:

 

1

 

Cut the pipe end with a pipe cutter.

 

2

 

Remove burrs with the cut surface facing downward so that the
chips do not enter the pipe.

 

3

 

Remove the flare nut from the stop valve and put the flare nut on
the pipe.

 

4

 

Flare the pipe. Set exactly at the position shown below.

 

5

 

Check that the flaring is properly made.

 

Connecting the refrigerant piping to the outdoor unit

 

1

 

To prevent gas leakage, apply refrigeration machine oil on both
inner and outer surfaces of the flare (use refrigeration oil for
R410A).

 

2

 

Align the centres of both flares and tighten the flare nuts 3 or 4
turns by hand. Then tighten them fully with torque wrenches.

Use torque wrenches when tightening the flare nuts to prevent
damage to the flare nuts and to prevent escaping of gas.

 

1

 

Drain-water hole

 

2

 

Bottom frame

 

3

 

Drain plug

 

4

 

Hose (field supply, inner diameter 16 mm)

 

1

 

Cut exactly at right angles.

 

2

 

Remove burrs

20

2
3

4

1

1

2

 

Flare tool for R410A 

(clutch type)

Conventional flare tool

Clutch type 

(Ridgid-type)

Wing nut type 

(Imperial-type)

 

A

0~0.5 mm

1.0~1.5 mm

1.5~2.0 mm

 

CAUTION

 

 

Do not use mineral oil on flared part.
Mineral oil getting into the system would reduce the
lifetime of the units.

 

 

Never use piping which has been used for previous
installations. Only use parts which are delivered with
the unit.

 

 

Do never install a drier to this R410A unit in order to
guarantee its lifetime. The drying material may
dissolve and damage the system.

 

 

Incomplete flaring may cause refrigerant gas leakage.

 

Flare nut

Flare nut tightening torque

 

Ø6.4 mm (1/4")

14.2~17.2 N•m

(144~175 kgf•cm)

Ø15.9 mm (5/8")

61.8~75.4 N•m

(630~769 kgf•cm)

A

1

2

3

1

Flare's inner surface must be flaw-free.

2

The pipe end must be evenly flared in a 
perfect circle.

3

Make sure that the flare nut is fitted.

1

2

3

4

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Содержание ERYQ005ACV3

Страница 1: ...INSTALLATION MANUAL ERYQ005ACV3 ERYQ006ACV3 ERYQ007ACV3 Outdoor unit for air to water heat pump ...

Страница 2: ...not use an extension cord Do not put other loads on the power supply use a dedicated power circuit Failure to do so may cause abnormal heat electric shock or fire Use the specified types of wires for electrical connections between the indoor and outdoor unit Firmly clamp the interconnecting wires so that their terminals receive no external stress Incomplete connections or clamping may cause termin...

Страница 3: ...like so that the operation noise will cause no trouble There must be sufficient space for carrying the unit into and out of the site There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet The site must be free from the possibility of flammable gas leakage in a nearby place Locate the unit so that the noise and the discharged hot air will not anno...

Страница 4: ...h between outdoor unit and indoor unit 3 m Maximum allowable height difference between outdoor unit and indoor unit 15 m Additional refrigerant required for refrigerant pipe exceeding 10 m in length 20 g m Gas pipe outer diameter 15 9 mm 5 8 Liquid pipe outer diameter 6 4 mm 1 4 100 350 1200 50 50 350 100 100 350 50 1 Wrap the insulation pipe with finishing tape from bottom to top 2 Service cover ...

Страница 5: ... the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the pipe Set exactly at the position shown below 5 Check that the flaring is properly made Connecting the refrigerant piping to the outdoor unit 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare use refrigeration oil for R410A 2 Align the centres of both flares and tigh...

Страница 6: ...ow pressure valve Lo and completely close its high pressure valve Hi The high pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling meter needle does not go back 5 Remove the covers ...

Страница 7: ...service sticker on the rear side of the stop valve cover Precautions when adding R410A Be sure to charge the specified amount of refrigerant in liquid state to the liquid pipe Since this refrigerant is a mixed refrigerant adding it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon...

Страница 8: ...op valve cover fit securely 3 1 Interconnection between indoor unit and outdoor unit when wire length exceeds 10 m use Ø2 5 mm wires instead of Ø1 5 mm wires 2 Power supply cable refer to the unit nameplate for maximum running current 3 Earth 4 Safety breaker 5 Earth leakage circuit breaker NOTE This unit must be earthed For earthing follow the applicable local standard for electrical installation...

Страница 9: ...nput may be higher than stated on the nameplate of the unit This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary...

Страница 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW33166 1B 3P194375 1A ...

Отзывы: