EKHWE150~3 E300A3Z2

Domestic hot water tank for air to water heat pump system

4PW43396-1B

 

Installation manual

 

3

 

Safety devices

 

 

Thermal protector — The booster heater in the domestic hot
water tank is equipped with a thermal protector. The thermal
protector is activated when the temperature becomes too high.
When activated, the protector has to be reset on the domestic
hot water tank by pressing the red button (for access, remove
the electrical box cover).

 

 

Pressure relief valve — A pressure relief valve (field supply) in
accordance with relevant local and national regulations, and with
an opening pressure of maximum 10 bar must be connected to
the pressure relief valve connection.

Water may drip from the discharge of the pressure relief valve
device.

 

Outlook diagram

 

Outlook diagram, see 

figure 2

.

 

Installation guidelines

 

Keep in mind the following guidelines when installing the domestic
hot water tank:

 

 

The installation location is frost-free.

 

 

Take  care that in the event of a leak, water cannot cause any
damage to the installation space and surroundings.

 

 

Make sure to make the piping in size 1" or more (and reduce to
3/4" at the inlet of the tank) as to have sufficient water volume in
the piping between indoor unit and domestic hot water tank.

 

 

Locate the domestic hot water tank in a suitable position to
facilitate ease of maintenance; remember access is required to
the electrical box. Refer to the grey-coloured zones indicated in

figure 2

.

 

 

Provide a connection for the pressure relief valve blow-off and
drain.

 

 

To  avoid back siphonage it is advised to install a non-return
valve on the water inlet of the domestic hot water tank in
accordance with local and national regulations.

 

Installing the domestic hot water tank

 

1

 

Check if all domestic hot water tank accessories (see

"Accessories" on page 1

) are enclosed.

 

2

 

When floor mounting, place the domestic hot water tank on a
level surface. If required, adjust the legs at the bottom. When
wall mounting (only for EKHWET150A3V3 model), make sure
the wall is sturdy. In both cases, make sure the domestic hot
water tank is mounted level.

 

3

 

Make sure to respect the service space as indicated in 

figure 2

.

 

Connecting the water circuits

 

Refer to the chapter "Typical application examples" described in the
installation manual delivered with the indoor unit for details on
connecting the water circuits and the motorised 3-way valve.

Make sure to insulate all water pipes and connections.

 

Connecting the 3-way valve

 

1

 

Refer to 

figure 3

 before making the connection.

 

2

 

Installation position.

It is advised to connect the 3-way valve as close as possible to
the indoor unit. It can be installed according the following four
configurations.

 

 

The domestic hot water tank relief valve connections
may not be used for other purpose.

 

 

Do not install heaters without thermal cut-outs.

 

The electrical box lid must only be opened by a
licensed electrician.

Switch off the power supply before opening the
electrical box lid.

 

figure A

figure B

figure C

figure D

 

1

 

From 

 

AD

 

 

 

indoor unit

 

2

 

To domestic hot water tank

 

3

 

To room heating

1

2

3

1

3

2

1

2

3

1

3

2

Содержание EKHWE150A3V3

Страница 1: ...INSTALLATION MANUAL EKHWE150A3V3 EKHWET150A3V3 EKHWE200A3V3 EKHWE300A3V3 EKHWE200A3Z2 EKHWE300A3Z2 Domestic hot water tank for air to water heat pump system ...

Страница 2: ...H2 20 40 H1 45 350 100 30 30 50 700 300 440 500 4 5 30 30 700 400 705 220 255 280 35 115 775 1150 13 21 355 440 50 EKHWE150 300 EKHWET150 D1 1150 775 280 255 35 545 1525 925 280 410 35 545 1525 851 210 410 27 660 H1 H2 H3 H4 H5 Ø D1 150 200 EKHWE 300 A A A A 16 16 16 400 400 0 400 2 1 3 ...

Страница 3: ... EKHWET150A3V3 EKHWE200A3V3 EKHWE200A3Z2 EKHWE300A3V3 EKHWE300A3Z2 Domestic hot water tank for air to water heat pump system Installation manual READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQU...

Страница 4: ...ng to EN directive 98 83 EC A drain device should be installed on the cold water connection on the domestic hot water tank For safety reasons it is not allowed to add ethylene glycol to the water circuit Adding ethylene glycol might lead to contamination of the domestic water if a leakage would occur in the heat exchanger coil It is important that the storage capacity of the domestic hot water tan...

Страница 5: ...ed in figure 2 Provide a connection for the pressure relief valve blow off and drain To avoid back siphonage it is advised to install a non return valve on the water inlet of the domestic hot water tank in accordance with local and national regulations Installing the domestic hot water tank 1 Check if all domestic hot water tank accessories see Accessories on page 1 are enclosed 2 When floor mount...

Страница 6: ...position as set during step 4 8 Put the red blue scale on the valve as shown below The red arrow will point to the red zone when the valve is in domestic water heating mode and will point to the blue zone when the valve is in room heating mode 9 Make the wiring in the indoor unit according to following figure Refer also to the drawing on page 6 Connecting the water circuits 1 Connect the water inl...

Страница 7: ...t be incorporated in the fixed wiring in accordance with relevant local and national legislation All field wiring and components must be installed by a licensed electrician and must comply with relevant European and national regulations The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below The domestic hot water tank must...

Страница 8: ...le ties to ensure strain relief 10 Set DIP switch SS2 2 on the PCB to ON 11 When routing out cables make sure that these do not obstruct mounting of the indoor unit cover Note only relevant field wiring is shown COMMISSIONING Before putting power to the unit make sure the unit is filled with water the sensor of the thermistor cable is mounted correctly in the thermistor socket a pressure relief va...

Страница 9: ...e that before starting any maintenance or repair activity also the power supply to the outdoor unit is switched off Do not use sharp metal tools or strong acid to remove the scaling Only use commercially available cleaning and scale removal agents for copper and enamelled surfaces After removing the scale rinse the domestic hot water tank by water jet It is of the utmost importance that the anode ...

Страница 10: ...4PW43396 1B Copyright Daikin 4PW43396 1 B 0000000S ...

Отзывы: