E(D/B)(H/L)Q011~0W1
Unit for air to water heat pump system
4PW51121-1C
Installation manual
16
Door 2: electrical parts of the hydraulic compartment: X10M
(1)(2)
Procedure
1
Using the appropriate cable, connect the power circuit to the
main circuit breaker as shown on the wiring diagram and in
figure 2
.
2
Connect the earth conductor (yellow/green) to the earthing
screw on the X1M terminal.
3
Fix the cable with cable ties to the cable tie mountings to ensure
strain relief. (Positions are marked with
in
figure 2
.)
Note: only relevant field wiring is shown.
4
If the backup heater capacity is to be set lower than the default
value (6 kW), this can be done by reconnecting wires according
to following figure. The backup heater capacity is now 3 kW for
V3 models or 2 kW for W1 models.
Connection of the thermostat cable
Connection of the thermostat cable depends on the application.
See also
"Typical application examples" on page 6
and
"Room
thermostat installation configuration" on page 19
for more information
and configuration options on pump operation in combination with a
room thermostat.
Thermostat requirements
■
Power supply: 230 V AC or battery operated
■
Contact voltage: 230 V.
Procedure
1
Connect the thermostat cable to the appropriate terminals as
shown on the wiring diagram.
2
Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
3
Set DIP switch SS2-3 on the PCB to ON. See
"Room thermostat
installation configuration" on page 19
for more information.
Connection of the valve control cables
Valve requirements
■
Power supply: 230 V AC
■
Maximum running current: 100 mA
Wiring the 2-way valve
1
Using the appropriate cable, connect the valve control cable to
the X2M terminal as shown on the wiring diagram.
2
Fix the cable(s) with cable ties to the cable tie mountings to
ensure strain relief.
Model
Backup heater
capacity
Backup heater
nominal voltage
Maximum
running current
Z
max
(
Ω
)
V3
(a) (b)
(a) Equipment complying with EN/IEC 61000-3-12
(1)
(b) This equipment complies with EN/IEC 61000-3-11
(2)
provided that the system
impedance Z
sys
is less than or equal to Z
max
at the interface point between the
user's supply and the public system. It is the responsibility of the installer or user
of the equipment to ensure, by consultation with the distribution network operator
if necessary, that the equipment is connected only to a supply with a system
impedance Z
sys
less than or equal to Z
max
.
6 kW
1x 230 V
26 A
0.29
W1
6 kW
3x 400 V
8.6 A
—
V3
(c)
(c) Refer to procedure how to set the backup heater to lower capacity.
3 kW
1x 230 V
13 A
—
W1
2 kW
3x 400 V
5.0 A
—
(1) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and
≤
75 A per phase.
(2) European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated current
≤
75 A.
NOTE
The earth leakage circuit breaker must be a
high-speed type breaker of 30 mA (<0.1 s).
L1
L3
L2
L1
L3
L2
1
2
X10M
X10M
V3
1~ 50 Hz
230 V
W1
3N~ 50 Hz
400 V
1
Earth leakage circuit
breaker
2
Fuse
V3
W1
1
2
3
4
5
6
1
2
3
4
5
6
E11H
E12H
E13H
E11H
E12H
E13H
X5M
BRN
BLK
GRY
X5M
1
2
3
4
5
6
1
2
3
4
5
6
E11H
E12H
E13H
E11H
E12H
E13H
X5M
BRN
BLK
GRY
X5M
1
2
3
4
1
2
3
4
E12H
ON
E12H
OFF
X5M
BLK
BRN
X5M
1
2
3
4
1
2
3
4
E12H
ON
E12H
OFF
X5M
BRN
BLK
X5M
Heating only thermostat
Heating/cooling thermostat
NOTE
Wiring is different for a NC (normal closed) valve
and a NO (normal open) valve. Make sure to
connect to the correct terminal numbers as
detailed on the wiring diagram and illustrations
below.
Normal closed (NC) 2-way valve
Normal open (NO) 2-way valve
X2M
H C
th
L N
1
2
3
4
X2M
H C
H
th
C
L N
1
2
3
4
NC
5
X2M
6
7
M
NO
5
6
X2M
7
M