2 LOCATION - GENERAL
2.11
Location:
The preferred Matrix Maxi location is on a smooth level floor, of
sufficient strength to support the filled weight of the Matrix Maxi, close to
the water source and a suitable overflow position (see Section 10 - Technical
Specification for filled weight). The Matrix Maxi must not be installed in a
loft space. It must also be considered that the noise and vibration from
the Matrix Maxi may be transmitted through the structure it is sited on.
Ensure the minimum clearance requirements are followed to allow servicing
of the unit
2.12
Access and minimum clearance requirements:
For emergencies and
maintenance the Matrix Maxi must be easily accessible and have the
minimum clearance around it as laid out in Fig. 2.
Additional access to the front of the unit will be required to operate the
keypad and view the display.
2.13
Protection:
The Matrix Maxi must be located in a dry, frost free area.
2.14
Ventilation:
Ensure an adequate air flow to cool the Matrix Maxi. Separate
the Matrix Maxi from other appliances that generate heat.
Do not
block the
vent holes on the front cover.
2.15
Water retention:
Site the Matrix Maxi in a location where in the unlikely
event of a water leak, any spillage is contained or routed to avoid electrics or
areas sensitive to water damage. As part of the AB airgap (CAT 5 fluid
isolation) the Matrix Maxi has a weir type overflow on the front, water will
be discharged from this area in the event of the failure of the inlet valve
or non-return valves.
2.16
Supply inlet pressure:
The water supply inlet pressure must not exceed 7 bar.
2.17
Ambient temperature:
The Matrix Maxi must be sited in a location where the ambient
temperature does not drop below 4 °C or exceed 40 °C.
2.18
Pipework:
For optimum performance inlet and outlet pipework must be a minimum of
15 mm pipe.