www.adelsystem.com
CBI - All in ONE
Model
CBI123A
CBI126A
CBI1210A
CBI1235A
CBI243A
CBI245A
CBI2410A
CBI2420A
CBI485A
CBI4810A
INPUT DATA
Nominal Input Voltage / Tensione d’ingresso nominale
115 – 230 – 277Vac
115 – 230 – 277Vac
115 – 230 – 277Vac
115 / 230 – 277Vac
115 – 230 – 277Vac
115 – 230 – 277Vac
115 / 230 – 277Vac
115 / 230 – 277Vac
115 / 230 – 277Vac
115 / 230 – 277Vac
Input Voltage Range / Campo di funzionamento
90 – 305Vac
90 – 305Vac
90 – 305Vac
90 – 135Vac
180 – 305Vac
90 – 305Vac
90 – 305Vac
90 – 135Vac
180 – 305Vac
90 – 135Vac
180 – 305Vac
90 – 135Vac
180 – 305Vac
90 – 135Vac
180 – 305Vac
Inrush Current (Vn and In Load) I
2
t / Corrente di Inserzione
d
11 A
d
5msec
d
11 A
d
5msec
d
11 A
d
5msec
d
35 A
d
5msec
d
11 A
d
5msec
d
11 A
d
5msec
d
16 A
d
5msec
d
35 A
d
5msec
d
16 A
d
5msec
d
35 A
d
5msec
Frequency /Frequenza di Ingresso
47 – 63 Hz ±6%
47 – 63 Hz ±6%
47 – 63 Hz ±6%
47 – 63 Hz ±6%
47 – 63 Hz ±6%
47 – 63 Hz ±6%
47 – 63 Hz ±6%
47 – 63 Hz ±6%
47 – 63 Hz ±6%
47 – 63 Hz ±6%
Input Current (115 – 230Vac) / Assorbimento
2.8 – 1.3A
2.8 – 1.3A
2.8 – 1.3A
8.0 – 4.2A
2.8 – 1.3A
2.8 – 1.3A
3.3 – 2.2A
8.0 – 4.2A
3.3 – 2.2A
8.0 – 4.2A
Internal Fuse / Fusibile Interno (non sostituibile)
4A
4A
4A
10A
4A
4A
6.3A
10A
6.3A
10A
External Fuse (recommended)/ Fusibile Esterno raccomandato
10A
10A
10A
16A
10A
10A
16A
16A
16A
16A
OUTPUT DATA
Output Vdc / I
N
/ Tensione di uscita Vdc / I
N
12Vdc – 3A
12Vdc – 6A
12Vdc – 10A
12Vdc – 35A
24Vdc – 3A
24Vdc – 5A
24Vdc – 10A
24Vdc – 20A
48Vdc – 5A
48Vdc – 10A
Output Current (In)
3A
6A
10A
35A
3A
5A
10A
20A
5A
10A
Dissipation Power load max (W)
9
17
17
28
13
17
28
54
28
54
Minimum load / Carico minimo
No
No
No
No
No
No
No
No
No
No
Efficiency (50% of In) / Rendimento tipico
90%
90%
90%
> 91%
90%
90%
83%
> 91%
83%
> 91%
Short-circuit protection / Protezione contro il corto circuito
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Over Load protection / Protezione sovraccarico
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Over Voltage Output protection / Protezione sovratensione in uscita
Yes (Typ. 35Vdc)
Yes (Typ. 35Vdc)
Yes (Typ. 35Vdc)
Yes (Typ. 35Vdc)
Yes (Typ. 35Vdc)
Yes (Typ. 35Vdc)
Yes (Typ. 35Vdc)
Yes (Typ. 35Vdc)
Yes (Typ. 90Vdc)
Yes (Typ. 90Vdc)
Overheating Thermal Protection / Protezione sovratemperatura
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Reverse battery protection / Protezione inversione batteria
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Sulfated battery check / Controllo batteria solfatata
Yes by Jumper
Yes by Jumper
Yes by Jumper
Yes by Jumper
Yes by Jumper
Yes by Jumper
Yes by Jumper
Yes by Jumper
Yes by Jumper
Yes by Jumper
Detection of element in short circuit / Relevazione elemento in corto circuito
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
LOAD OUTPUT / USCITA CARICO
Output voltage (at at IN) Vdc / Tensione di uscita (a IN) Vdc
10 – 14.4Vdc
10 – 14.4Vdc
10 – 14.4Vdc
10 – 14.4Vdc
22 – 28.8Vdc
22 – 28.8Vdc
22 – 28.8Vdc
22 – 28.8Vdc
44 – 57.6Vdc
44 – 57.6Vdc
Nominal Current IN = Iload
1.1 x In A ± 5%
1.1 x In A ± 5%
1.1 x In A ± 5%
1.1 x In A ± 5%
1.1 x In A ± 5%
1.1 x In A ± 5%
1.1 x In A ± 5%
1.1 x In A ± 5%
1.1 x In A ± 5%
1.1 x In A ± 5%
Continuous current (without battery) Iload = In
3A
6A
10A
35A
3A
5A
10A
20A
5A
10A
Max continuous current (with battery) Iload = In + Ibatt
6A
12A
20A
70A
6A
10A
20A
40A
10A
20A
Max current Output Load: (Main Input) Iload (4sec.)
9A max
18A max
30A max
105A max
9A max
15A max
30A max
60A max
15A max
30A max
Max current Output Load: (Back Up) Iload (4sec.)
6A max
12A max
20A max
70A max
6A max
10A max
20A max
40A max
10A max
20A max
Push Button or Remote Input Control (AMP type connector)
Start from Battery without main
Start from Battery without main
Start from Battery without main
Start from Battery without main
Start from Battery without main
Start from Battery without main
Start from Battery without main (1)
Start from Battery without main
Start from Battery without main (1)
Start from Battery without main
Time Buffering; min (switch output off without main input)
Can be aduste by PC SW mode
Can be aduste by PC SW mode
Can be aduste by PC SW mode
0.5;1;3;5;10;15; 20; 30; 45;60;
Can be aduste by PC SW mode
Can be aduste by PC SW mode
5 min standard - Require: SW S31
0.5;1;3;5;10;15; 20; 30; 45;60;
5 min standard - Require: SW S31
0.5;1;3;5;10;15; 20; 30; 45;60;
Protections against total discharge
9 – 10 Vdc batt
9 – 10 Vdc batt
9 – 10 Vdc batt
9 – 10 Vdc batt
19 – 20 Vdc batt
19 – 20 Vdc batt
19 – 20 Vdc batt
19 – 20 Vdc batt
38 – 40 Vdc batt
38 – 40 Vdc batt
Threshold alarm Battery almost flat
10 – 11 Vdc batt
10 – 11 Vdc batt
10 – 11 Vdc batt
10 – 11 Vdc batt
20 – 21 Vdc batt
20 – 21 Vdc batt
20 – 21 Vdc batt
20 – 21 Vdc batt
40 – 42 Vdc batt
40 – 42 Vdc batt
BATTERY CHARGER OUTPUT / USCITA CARICA BATTERIA
Boost – Bulk charge (Typ. at I
N
) / Carica Veloce
14.4Vdc
14.4Vdc
14.4Vdc
14.4Vdc
28.8Vdc
28.8Vdc
28.8Vdc
28.8Vdc
57.6
57.6
Max.Time Boost–Bulk charge (Typ. at I
N
) / Tempo massimo Carica Veloce
15h
15h
15h
15h
15h
15h
15h
15h
15h
15h
Min.Time Boost–Bulk charge (Typ. at I
N
) / Tempo minimo Carica Veloce
1min.
1min.
1min.
1min.
1min.
1min.
1min.
1min.
1min.
1min.
Trickle-Float charge (Typ. at I
N
) / Carica di mantenimento
13.75Vdc
13.75Vdc
13.75Vdc
13.75Vdc
27.5Vdc
27.5Vdc
27.5Vdc
27.5Vdc
55Vdc
55Vdc
Recovery Charge / Carica di recupero
2 – 9Vdc
2 – 9Vdc
2 – 9Vdc
2 – 9Vdc
2 – 16Vdc
2 – 16Vdc
2 – 16Vdc
2 – 16Vdc
2 – 24Vdc
2 – 24Vdc
Turn-On delay after applying mains voltage / Accensione con tensione di rete
1sec. Max
1sec. Max
1sec. Max
1sec. Max
1sec. Max
1sec. Max
1.5sec. Max
1sec. Max
1.5sec. Max
1sec. Max
End of charging current (Bulk charge)
0.3A
0.3A
0.3A
0.3A
0.3A
0.3A
0.3A
Start up with strong load (capacitive load)/ Start up con carichi capacitivi
Yes, Unlimited
Yes, Unlimited
Yes, Unlimited
Yes, Unlimited
Yes, Unlimited
Yes, Unlimited
Yes, Unlimited
Yes, Unlimited
Yes, Unlimited
Yes, Unlimited
Residual Ripple / Ripple Residuo
d
60 mVpp
d
60 mVpp
d
60 mVpp
d
60 mVpp
d
60 mVpp
d
60 mVpp
d
60 mVpp
Charging max I
batt
/ Corrente max. di Carica
3A ± 5%
6A ± 5%
10A ± 5%
35A ± 5%
3A ± 5%
5A ± 5%
10A ± 5%
10A ± 5%
5A ± 5%
10A ± 5%
Charging current Limiting I
N
(I
adj
) / Limitazione Corrente di Carica
20 ÷ 100 % / I
batt
20 ÷ 100 % / I
batt
20 ÷ 100 % / I
batt
10 ÷ 100 % / I
batt
20 ÷ 100 % / I
batt
20 ÷ 100 % / I
batt
20 ÷ 100 % / I
batt
10 ÷ 100 % / I
batt
20 ÷ 100 % / I
batt
10 ÷ 100 % / I
batt
Jumper Config.Type Battery (NiCd optional)/Configurazione Tipo Batteria
Quieshent Current / Consumo da batteria max.
5mA
5mA
5mA
5mA
5mA
5mA
5mA
5mA
5mA
5mA
Remote Input Control (AMP Type connector)
Boost / Trickle
Boost / Trickle
Boost / Trickle
Boost / Trickle
Boost / Trickle
Boost / Trickle
Boost / Trickle
Boost / Trickle
Boost / Trickle
Boost / Trickle
Characteristic Curve / Caratteristiche di Carica
SIGNAL OUTPUT (RELAY) / SEGNALAZIONE RELÈ USCITA
Main or Backup Power
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Low Battery
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Fault Battery
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
AUXILIARY OUTPUT (RJ 45 CONNECTION) FOR:
CAN Bus
No
No
No
Optional
No
No
No
Optional
No
Optional
CLIMATIC DATA
Ambient Temperature operation / Temperatura Ambiente di Lavoro
-25 ÷ +70°C
-25 ÷ +70°C
-25 ÷ +70°C
-25 ÷ +70°C
-25 ÷ +70°C
-25 ÷ +70°C
-25 ÷ +70°C
-25 ÷ +70°C
-25 ÷ +70°C
-25 ÷ +70°C
De rating Tª > (In) / De rating Tª > (In)
> 50° -2.5%(In) / °C
> 50° -2.5%(In) / °C
> 50° -2.5%(In) / °C
> 50° -2.5%(In) / °C
> 50° -2.5%(In) / °C
> 50° -2.5%(In) / °C
> 50° -2.5%(In) / °C
> 50° -2.5%(In) / °C
> 50° -2.5%(In) / °C
> 50° -2.5%(In) / °C
Ambient Temperature Storage / Temperatura max. Magazzino
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
Humidity at 25 °C
/
Umidità
95% to 25°C
95% to 25°C
95% to 25°C
95% to 25°C
95% to 25°C
95% to 25°C
95% to 25°C
95% to 25°C
95% to 25°C
95% to 25°C
Cooling / Raffreddamento
Auto Convection
Auto Convection
Auto Convection
Auto Convection
Auto Convection
Auto Convection
Auto Convection
Auto Convection
Auto Convection
Auto Convection
GENERAL DATA
Isolation Voltage (IN / OUT) / Tensione di Isolamento (IN / OUT)
3000Vac
3000Vac
3000Vac
3000Vac
3000Vac
3000Vac
3000Vac
3000Vac
3000Vac
3000Vac
Isolation Voltage(IN / PE) / Tensione di Isolamento(IN / TERRA)
1605Vac
1605Vac
1605Vac
1605Vac
1605Vac
1605Vac
1605Vac
1605Vac
1605Vac
1605Vac
Isolation Voltage(OUT / PE) / Tensione di Isolamento(OUT/TERRA)
500Vac
500Vac
500Vac
500Vac
500Vac
500Vac
500Vac
500Vac
500Vac
500Vac
Protection Class (EN/IEC 60529) / Protezione Classe
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
Reliability (MTBF IEC 61709) / Affidabilità
> 300 000 h
> 300 000 h
> 300 000 h
> 300 000 h
> 300 000 h
> 300 000 h
> 300 000 h
> 300 000 h
> 300 000 h
> 300 000 h
Pollution Degree Environment / Grado d'inquinamento ambientale
2
2
2
2
2
2
2
2
2
2
Connection Terminal Blocks Screw Type / Dimensione morsetti
2,5mm (24-14 AWG)
2,5mm (24-14 AWG)
2,5mm (24-14 AWG)
4mm (30-10 AWG)
2,5mm (24-14 AWG)
2,5mm (24-14 AWG)
2,5mm (24-14 AWG)
4mm (30-10 AWG)
2,5mm (24-14 AWG)
4mm (30-10 AWG)
Protection class (with PE connected) /
Grado di protezione (con cavo di terra collegato)
I
I
I
I
I
I
I
I
I
I
Dimension (w-h-d)/Dimensioni (l-h-p) mm
65x115x135 mm
65x115x135 mm
65x115x135 mm
150x115x135 mm
65x115x135 mm
65x115x135 mm
100x115x135 mm
150x115x135 mm
100x115x135 mm
150x115x135 mm
Weight / Peso
0.60 kg approx
0.60 kg approx
0.60 kg approx
1.55 kg approx
0.60 kg approx
0.60 kg approx
0.85 kg approx
1.55 kg approx
0.85 kg approx
1.55 kg approx
Safety Standard Approval / Conformità ed Approvazioni
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
(1) - Options to be defined by Order, Push Button not available
Optional for auxiliary Output (RJ45 connection):
Temp Charging probe: Temperature sensor for battery 2m lenght. Voltage drop compensation: Cable for battery connection 2m lenght. Remote monitoring Display. Can Bus Cable.
IUoUo, Automatic, 3 stage / IUoUo, Automatico a 3 Stadi
12Vdc
24Vdc
48Vdc
2.23 V/cell Open Lead, 2.25 V/cell Sealed Lead, 2.27 V/cell Sealed Lead, 2.3 V/cell gel;
NiCd 1.5V/cell (10 elem.) trickle (Imax 10%)
2.23 V/cell Open Lead, 2.25 V/cell Sealed Lead, 2.27 V/cell Sealed Lead, 2.3 V/cell gel;
NiCd 1.5V/cell (20 elem.) trickle (Imax 10%)
2.23 V/cell Open Lead, 2.25 V/cell Sealed Lead,
2.27 V/cell Sealed Lead, 2.3 V/cell gel;
NiCd 1.5V/cell (40 elem.) trickle (Imax 10%)
All specification are subject to change without notice
Rev. 09 - 2011