INITIAL RUN PROCEDURE

After start up and checks are complete and after the main electrical power to the dryer has  been 

connected, follow the  procedure below to put the dryer in operation:  

1. Turn ON the dryer ON/OFF switch.

2.

Let the dryer run for 15 minutes.  

IMPORTANT NOTE: All 230/460/575 VAC, 3 Phase motors MUST be wired for proper rotation.  

After the air dryer is turned ON, the suction pressure should DECREASE (pull down) instantly.  If 

the suction pressure  does not pull down TURN OFF THE AIR DRYER IMMEDIATELY and contact 

your local distributor or Altec AIR for assistance   

3.

Check the Refrigerant Suction Pressure (on Gauge UA75/MHT40 and above):

R134a dryers. (28 psig to 34 psig)

R404a dryers. (72 psig to 80 psig)

4.

Check the Refrigerant Discharge Pressure (on Gauge UA400/MHT200 and above):

R134a dryers. (90 psig to 150 psig)

R404a dryers. (220 psig to 350 psig)

5.

Verify that the condenser fan motors are operating. On units UA400/MHT200 and above fan will cycle 

ON and OFF as follows: 

FAN 1  R404a dryers. (ON at 230 PSIG, OFF at 135 PSIG)

FAN 2  R404a dryers. (ON at 275 PSIG, OFF at 195 PSIG)

5.

Allow compressed air to flow through the dryer.

6.

Confirm that condensate is discharging from the condensate drain. This may take 30-60 minutes.

7.

Make sure bypass valves are closed and 100% of the air from the compressor is flowing 

through the dryer.

HOW TO SET THE CONDENSATE DRAIN OPEN & 

CLOSED TIME (LOCATE DRAIN VALVE)

The OPEN (ON) time is adjustable from 0.5 sec to 10 sec. Drains are 

set at factory to open for 6 sec. When drain opens the on light will light

The CLOSED (OFF) time is adjustable 0.5 min to 45 min. Drains are set 

at factory to  stay closed for 10 min. When drain is closed the off light 

will light.

You may increase or decrease this based on moisture levels in the air. 

Push the TEST button to manually open the drain valve.

TO CLEAN VALVE

1. Close isolation valve

2. Push the push to test button to release the 

pressure

3. Remove strainer/filter and screen. 

4. Clean screen and replace.

Содержание MHT Series

Страница 1: ...Please record the information below and keep this manual If you need service on this dryer you will need this information Model _____________________________ Serial ______________________________ Volt...

Страница 2: ...the factory Authorization must be obtained from Altec AIR before any parts or dryers are returned to the factory Altec AIR will not be responsible for anything returned without authorization RECEIVIN...

Страница 3: ...pressurizing proper maintenance and servicing of the air dryer Condensate drains must be properly piped from the dryer to prevent moisture re entrainment The dryer is equipped with an automatic drain...

Страница 4: ...XA After filter 7 3 Valve Bypass 8 UA MHT Series non cycling air dryer 9 AW Series Water Separator 10 Centrifugal separator INSTALLATION A Recommended for systems that consume less than or equal to t...

Страница 5: ...s down dryer in the event of overload conditions Installed on UA150 MHT100 and above 10 Low Pressure Shutdown Shuts down the dryer in the event of low ambient temps or if there is a refrigerant leak i...

Страница 6: ...SSURE SHUTDOWN Shuts the dryer down in the event of low ambient conditions or if there is a leak in the refrigeration system Installed on UA400 MHT200 and above START UP The following procedure must b...

Страница 7: ...n motors are operating On units UA400 MHT200 and above fan will cycle ON and OFF as follows FAN 1 R404a dryers ON at 230 PSIG OFF at 135 PSIG FAN 2 R404a dryers ON at 275 PSIG OFF at 195 PSIG 5 Allow...

Страница 8: ...ling to condense entrained moisture out of the compressed air stream Warm saturated air enters the air to air heat exchanger at the dryer inlet In the air to air heat exchanger the inlet air is pre co...

Страница 9: ...ad on the dryer changes the suction pressure will change An increase in air flow causes an increase in suction pressure a decrease in air flow causes a decrease in suction pressure During periods of l...

Страница 10: ...er is on to the dryer but the dryer will not start Fuse is bad Check for short fix and replace fuse On Off switch defective Replace switch No power going to dryer Check circuit breaker and power suppl...

Страница 11: ...11 UA40 UA55 MHT25 UA20 UA25 TECHNICAL SPECIFICATIONS...

Страница 12: ...12 UA200 3 4 5 MHT130 3 4 5 UA75 UA100 UA125 UA150 UA200 1 2 MHT40 MHT60 MHT75 MHT100 MHT130 1 2...

Страница 13: ...13 UA250 UA300 MHT150 UA400 UA500 UA625 MHT200...

Страница 14: ...14 UA800 UA1000 UA1200 UA1600 UA2000...

Страница 15: ...15 DATA LABEL UA Series Note Data below is for reference only and is subject to change Please refer to the label on your unit for the most up to date information...

Страница 16: ...16 DATA LABEL MHT Series Note Data below is for reference only and is subject to change Please refer to the label on your unit for the most up to date information...

Страница 17: ...17 ELECTRICAL SCHEMATICS UA20A UA25A UA40A UA55A MHT25A UA75A UA100A UA125A MHT40A MHT60A MHT75A UA150A UA200A UA250A UA300A MHT100A MHT130A MHT150A...

Страница 18: ...18 ELECTRICAL SCHEMATICS UA200A UA250A UA300A MHT130A MHT150A...

Страница 19: ...19 ELECTRICAL SCHEMATICS UA400A UA500A UA625A UA800A UA1000A UA1200A MHT200A...

Страница 20: ...20 ELECTRICAL SCHEMATICS UA1600A UA2000A...

Страница 21: ...y 2 Check actual ambient temp to rated temp 3 Check actual inlet temp to rated inlet temp 4 Check actual inlet psig to rated inlet psig 5 Make sure condenser is always clean 6 Clean drain regularly Us...

Страница 22: ...22 226A COMMERCE ST BROOMFIELD CO 80020 1 800 521 5351 303 657 2205 sales AltecAIR com www AltecAIR com NOTES...

Отзывы: