P846/EN IN/D
Installation
(IN) 15-8
MiCOM P846
IN
6.
RELAY WIRING
This section serves as a guide to selecting the appropriate cable and connector type for
each terminal on the relay.
6.1
Medium and heavy duty terminal block connections
Key:
Heavy duty terminal block:
CT and VT circuits, terminals with “D” prefix
Medium duty:
All other terminal blocks (grey color)
Loose relays are supplied with sufficient M4 screws for making connections to the rear
mounted terminal blocks using ring terminals, with a recommended maximum of two ring
terminals per relay terminal.
If required, Alstom Grid can supply M4 90° crimp ring terminals in three different sizes
depending on wire size (see Table 3). Each type is available in bags of 100.
Part Number
Wire Size
Insulation Color
ZB9124 901
0.25 - 1.65mm
2
(22 - 16AWG)
Red
ZB9124 900
1.04 - 2.63mm
2
(16 - 14AWG)
Blue
ZB9124 904
2.53 - 6.64mm
2
(12 - 10AWG)
Un-insulated*
Table 3:
M4 90° crimp ring terminals
*To maintain the terminal block insulation requirements for safety, an insulating sleeve
should be fitted over the ring terminal after crimping.
The following minimum wire sizes are recommended:
Current Transformers
2.5mm
2
Auxiliary Supply, Vx
1.5mm
2
EIA(RS)485 Port
See separate section
Other Circuits
1.0mm
2
Due to the limitations of the ring terminal, the maximum wire size that can be used for any of
the medium or heavy duty terminals is 6.0mm
2
using ring terminals that are not pre-
insulated. Where it required to only use pre-insulated ring terminals, the maximum wire size
that can be used is reduced to 2.63mm
2
per ring terminal. If a larger wire size is required,
two wires should be used in parallel, each terminated in a separate ring terminal at the relay.
The wire used for all connections to the medium and heavy duty terminal blocks, except the
EIA(RS)485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary supply wiring should be protected by a 16A high rupture
capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits
must never be fused. Other circuits should be appropriately fused to protect the wire used.
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......